Annotations

A-02-01 Aluminium window system (Inward opening side-hung window)

General Information: The Aluminium Window System (Inward Opening Side-Hung Window) is designed for glazing building openings with inward-opening side-hinged functionality. The system provides natural ventilation, airtight closure, and an aesthetically integrated façade appearance, while maintaining compatibility with both curtain wall and integrated façade systems.

Energy / Thermal Considerations: The system must ensure a low thermal transmittance (U-value), minimised heat loss, and prevention of condensation on profiles. Multi-chamber aluminium profiles with thermal breaks and insulated glazing units (IGUs) featuring low-emissivity coatings and inert gas filling are used. These requirements are regulated by BS EN ISO 10077 (Thermal performance of windows) and BS EN 1279 (Insulating glass units).

Technical Considerations: The aluminium profile and hardware must provide strength, airtightness, ease of operation, and long-term durability. Profiles shall comply with BS EN 755 and BS EN 12020, while the overall system design shall conform to BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures) and BS EN 14351-1 (Windows and doors – Product standard). Seals must comply with BS EN 12365 to ensure water and air tightness.

Fire Safety Considerations: Aluminium is classified as a non-combustible material (Class A1 according to BS EN 13501-1). The fire performance of the window system depends on the glazing and seal components. For use in areas with higher fire safety requirements, fire-rated glass units and seals certified in accordance with BS EN 13501-2 must be used.

Design Life: The expected service life of the Inward Opening Side-Hung Aluminium Window is 30 years, provided that installation, operation, and maintenance are carried out in accordance with BS EN 1999-1-1 and BS EN 14351-1.

Testing Regime: Testing includes:

  • Thermal transmittance — BS EN ISO 10077;

  • Water and air tightness — BS EN 1027 / BS EN 12207;

  • Resistance to wind load — BS EN 12210;

  • Durability of hardware and seals;

  • Fire resistance — BS EN 13501-2 using certified fire-resistant glazing.

 

A-03-04 Aluminium balcony door system (Sliding door)

General Information: The Aluminium Balcony Door System (Sliding Door) is an aluminium sliding door system used for access to balconies and terraces. It provides transparency, natural daylight and ease of operation, combining the compact functionality of a sliding mechanism with the durability of an aluminium construction.

Energy / Thermal Considerations: The system must provide adequate thermal insulation for external building envelope applications. Aluminium profiles shall incorporate a thermal break compliant with BS EN 14024, and thermal transmittance values must be verified through calculations and testing in accordance with BS EN ISO 10077-1 and BS EN ISO 10077-2. Insulated glazing units (IGUs) shall provide high thermal resistance and comply with BS EN 1279.

Technical Considerations: Aluminium profiles shall comply with BS EN 755 and BS EN 12020 regarding material properties, geometry and fabrication. The sliding mechanism must ensure smooth operation, resistance to wind loads and effective weather performance in accordance with:

  • BS EN 12207 (Air permeability)

  • BS EN 12208 (Watertightness)

  • BS EN 12210 (Resistance to wind load)

Structural design must be undertaken in accordance with BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures).

Fire Safety Considerations: Aluminium profiles are classified as A1 under BS EN 13501-1 and are non-combustible. Where fire performance is required, the behaviour of the door assembly shall be assessed in accordance with BS EN 1634-1 (Fire resistance tests for doors). IGUs must meet the fire performance criteria of the overall system, and if the door is integrated into a façade system, it shall form part of overall fire testing under BS EN 13501-2 and BS 8414.

Design Life: The expected service life of the Aluminium Balcony Door System (Sliding Door) is at least 30 years, provided that correct installation, regular maintenance of the sliding mechanism, and appropriate protective finishes are ensured, in accordance with BS EN 1999 and BS EN 12206.

Testing Regime: The system must be tested for air permeability, watertightness and resistance to wind load in accordance with BS EN 12207, BS EN 12208 and BS EN 12210. IGUs must be tested in accordance with BS EN 1279, and mechanical components are subject to durability and wear testing in accordance with BS EN 13126-19 (Sliding fittings)

 

C-01-01 Aluminium support bracket (Aluminium cladding)

General information: The aluminium support bracket is used to fix aluminium cladding panels to façade structures, providing stability and accurate positioning of the cladding elements. It ensures long-term fixation under various loads and weather conditions.

Energy / Thermal considerations:
The element has the high thermal conductivity of aluminium, which must be accounted for regarding expansion and contraction due to temperature changes. The design should minimise thermal bridging, in compliance with BS EN ISO 6946 and BS EN 13947, to maintain thermal efficiency of the façade system.

Technical considerations:
The bracket must withstand static and dynamic loads, including the weight of cladding panels, wind loads, and potential seismic actions, in accordance with BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures). Only corrosion-resistant aluminium alloys with anodised or powder-coated finishes are permitted to ensure durability.

Fire safety considerations:
Aluminium brackets are non-combustible; however, their use must be compatible with the fire performance of the façade system. Cladding materials should be classified A2-s1,d0 according to BS EN 13501-1 to minimise fire spread and smoke emission.

Design life:
The expected service life of aluminium support brackets is 30 years, according to BS EN 1999-1-1, provided proper installation and operation in line with performance requirements.

Testing regime:
Brackets should be tested for strength and durability, including corrosion resistance (BS EN ISO 9227) and mechanical load testing (BS EN 1990, BS EN 1999-1-1)

 

C-01-02 Aluminium L-profile

General Information: An aluminium L-profile is an angular extrusion commonly used in ventilated façade systems for fixing, aligning, and joining cladding panels, as well as reinforcing corners and edges of the façade structure. It serves as part of the subframe in both external rainscreen systems and internal wall assemblies, providing structural alignment and support.

Energy / Thermal Considerations: Due to aluminium’s high thermal conductivity, L-profiles can act as localised thermal bridges. To reduce adverse impacts on the thermal performance of the façade system, thermal isolators or breaks should be used where profiles penetrate or interact with the insulation layer. Thermal impact should be assessed in accordance with BS EN ISO 10211 (thermal bridge modelling) and BS EN ISO 6946 (thermal transmittance).

Technical Considerations: The profile should be manufactured from aluminium or aluminium alloys compliant with BS EN 573-3 (chemical composition) and BS EN 755 (mechanical properties and tolerances). It must demonstrate sufficient stiffness and dimensional stability under wind, dead, and service loads. Surface treatment such as anodising or polyester powder coating is recommended for external use in accordance with BS EN 12206, ensuring corrosion resistance and durability.

Fire Safety Considerations: Aluminium is classified as non-combustible (Class A1 under BS EN 13501-1). However, it loses mechanical strength at temperatures exceeding 300–400 °C. Therefore, in fire-critical zones or components contributing to fire barriers, its use must be justified through system-level fire testing in accordance with BS 8414 and performance evaluation to BR 135.

Design Life: The expected service life of an aluminium L-profile is at least 30 years, provided proper detailing, installation, and corrosion protection are ensured. Structural design should comply with BS EN 1999 (Eurocode 9 – Design of aluminium structures) and manufacturing standards such as BS EN 1090-1 for CE marking and fabrication control.

Testing Regime: Performance testing includes:

  • Mechanical strength and deflection resistance per BS EN ISO 6892-1 (tensile properties);

  • Corrosion resistance assessment through salt spray testing as per BS EN ISO 9227;\

  • Fire behaviour assessment as part of the façade system in accordance with BS 8414 and classification per BS EN 13501-1 (Class A1).

 

D-06-01 Stainless steel support bracket (Window)

General Information: The stainless steel support bracket for windows is used to fix window frames to the primary building structure, ensuring the transfer of operational and wind loads, and securing the window units in their designed position.

Energy / Thermal Considerations: In accordance with BS EN 10077 and BS EN ISO 6946, the bracket must be installed to minimise thermal bridging. The use of thermal insulating pads or combined fixing assemblies helps reduce heat loss and maintain the designed thermal transmittance (U-value) of the window system.

Technical Considerations: The bracket must comply with BS EN 1090 (fabrication of steel structures) and BS EN 10088 (stainless steel — mechanical properties and corrosion resistance). The design must withstand static and dynamic loads from the window unit in accordance with BS EN 14351-1 (windows and doors) and BS EN 1991 (structural loads).

Fire Safety Considerations: According to BS EN 13501-1, stainless steel is classified as A1, ensuring it is non-combustible, produces no smoke, and does not contribute to fire development.

Design Life: The expected service life of the window support bracket is at least 30 years, provided that the stainless steel grade is selected in accordance with BS EN 10088 and the fixing details are properly designed in accordance with BS EN 1090.

Testing Regime: Testing must be carried out in accordance with BS EN 1090 to confirm load-bearing capacity and compliance with design loads, and BS EN ISO 3506 to verify the properties of stainless steel. Additional testing may be carried out in accordance with BS EN 14609 (mechanical performance of window fixings).

 

D-07-01 Stainless steel subsystem

General Information: The Stainless Steel Subsystem is used in ventilated rainscreen façade systems for fixing cladding panels to the building’s load-bearing structure. The system provides stable and durable support, transfers wind and service loads, and allows for thermal movement of façade panels.

Energy / Thermal Considerations: The subsystem must be compatible with the façade insulation and designed to minimise thermal bridging. Thermal breaks and insulating pads are used to reduce heat loss. Thermal performance requirements are governed by BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: The stainless steel subsystem must demonstrate high strength and resistance to deformation under wind and operational loads. Materials and connections shall comply with BS EN 10088 (Stainless steels – Technical delivery conditions), and structural design shall conform to BS EN 1993-1-1 and BS EN 1993-1-8 (Eurocode 3: Design of steel structures and joints). All components must be corrosion-resistant for external use, including in aggressive atmospheric environments.

Fire Safety Considerations: Stainless steel is classified as non-combustible, Class A1 according to BS EN 13501-1. The system does not contribute to flame spread and retains structural integrity under elevated temperatures in accordance with BS EN 1993-1-2 (Structural fire design). The fire performance of the complete façade assembly must be verified in accordance with BS EN 13501-2 and BS 8414.

Design Life: The expected service life of the Stainless Steel Subsystem is at least 50 years, provided that correct installation and maintenance are observed, and an appropriate grade of stainless steel (e.g. A4) is used, in accordance with BS EN 10088 and BS EN 1993.

Testing Regime: Testing shall include:

  • Mechanical strength and joint durability — BS EN 13144;

  • Corrosion resistance — BS EN ISO 9227;

  • Fire resistance of the façade system — BS EN 13501-2 and BS 8414

 

E-03-01 Stainless steel cast-in channel

General information: Stainless steel cast-in channels are used as embedded elements in concrete structures to securely fix façade systems, engineering services, and other building components. Stainless steel channels are embedded in concrete during casting, providing a durable and safe solution for load transfer.

Energy / Thermal considerations: In accordance with BS EN ISO 10077 and BS EN 1993, stainless steel elements have minimal impact on the thermal performance of the building envelope. Where thermal bridging needs to be minimised, solutions with thermal breaks or composite connections are applied to meet façade energy efficiency requirements.

Technical considerations: In accordance with BS EN 1993-1-4 and BS EN 1090, stainless steel channels must provide high load-bearing capacity, corrosion resistance, and fatigue durability. The material complies with BS EN 10088 (stainless steel), and the geometry and welded joints are manufactured in accordance with the execution class requirements of BS EN 1090-2. Special anchors are used to ensure even load distribution and reliable bonding with concrete.

Fire safety considerations: In accordance with BS EN 13501-1, stainless steel is classified as a non-combustible material of class A1, ensuring no flammability or smoke generation. When used as part of façade systems and concrete structures, the channels do not contribute to fire spread and maintain structural integrity under high temperatures within the standard fire resistance period (BS EN 1993-1-2).

Design life: Expected design life: 50 years according to BS EN 1993-1-4. Selecting the appropriate stainless steel grade (e.g., AISI 304 or 316 according to BS EN 10088) ensures a long service life in exterior conditions without significant loss of strength or corrosion resistance.

Testing regime: In accordance with BS EN 1993 and BS EN 1090, the elements are tested for strength, load-bearing capacity, and welded joint durability. Additional tests are conducted for corrosion resistance in accordance with BS EN ISO 9227 (salt spray chamber testing) and for anchor adhesion in concrete in accordance with BS EN 1881.

 

E-03-02 Stainless steel T-bolt (nut+washer)

General information: The stainless steel T-bolt (supplied with nut and washer) is used to fix façade systems, equipment, and structural elements to cast-in channels or other mounting profiles. It provides fast and reliable installation without the need for welding or drilling and is used in construction and mechanical engineering.

Energy / Thermal considerations: In accordance with BS EN ISO 10077 and BS EN 1993, the T-bolt has minimal impact on the thermal performance of the structures. In façade systems, where thermal bridging needs to be minimised, fixing points can be supplemented with thermal breaks or pads to meet energy efficiency requirements.

Technical considerations: In accordance with BS EN ISO 3506 (mechanical properties of stainless steel fasteners), the T-bolt must provide tensile, torsional, and fatigue strength. Thread dimensions and tolerances are manufactured in accordance with BS EN ISO 898 and BS EN ISO 965. Washers and nuts are made in accordance with BS EN ISO 7089/7090 and BS EN ISO 4032, ensuring compatibility and reliability of the threaded connection. The design ensures even load transfer within the “channel–bolt–nut” system.

Fire safety considerations: According to BS EN 13501-1, stainless steel is classified as A1 (non-combustible), eliminating flammability and smoke emission. Under high temperatures, the load-bearing capacity is maintained up to the design limit according to BS EN 1993-1-2, ensuring reliable fixing performance in fire conditions.

Design life: Expected design life: 50 years according to BS EN ISO 3506 and BS EN 1993-1-4. The use of corrosion-resistant steel grades A2 or A4 according to BS EN 10088 ensures long-term durability even in exterior environments with aggressive conditions.

Testing regime: In accordance with BS EN ISO 3506, mechanical strength and torque tests are conducted. Corrosion resistance is tested in accordance with BS EN ISO 9227 (salt spray). For façade systems, the T-bolt is additionally tested for compliance with channel fixation and load-holding capacity requirements according to BS EN 1090

 

F-01-01 Stainless steel screw

General Information: Stainless steel screws are utilised for securing structures and materials, offering high strength and corrosion resistance. They are suitable for both interior and exterior applications, including aggressive environments.

Energy / Thermal Considerations: Stainless steel screws exhibit low thermal conductivity, reducing the risk of thermal bridging. In accordance with BS EN ISO 10144, their corrosion resistance is maintained at high and low temperatures, making them suitable for diverse climatic conditions.

Technical Considerations: Screws must comply with BS EN ISO 3506 for mechanical properties and corrosion resistance. Strength classes (e.g., A2, A4) determine their suitability for different environments. Protective coatings are recommended for use in highly corrosive conditions.

Fire Safety Considerations: Stainless steel is classified as a non-combustible material (Class A1 per BS EN 13501-1). The screws do not contribute to flame spread or emit toxic substances when exposed to heat.

Design Life: The expected service life is at least 30 years under standard conditions, as per BS EN ISO 9224, owing to their high corrosion resistance.

Testing Regime: Quality control includes:

  • Tensile testing (BS EN ISO 6892-1)

  • Hardness testing

  • Corrosion resistance testing (BS EN ISO 9227 – salt spray test)

 

F-01-02 Stainless steel screw (big)

General Information: The Stainless Steel Screw (Big) is used for fastening structural or façade elements where enhanced load-bearing capacity is required. It is commonly applied in rainscreen cladding systems, roofing, and structural connections to transfer high loads and ensure joint rigidity.

Energy / Thermal Considerations: Stainless steel has high thermal conductivity, which can create thermal bridges at fixing points. To minimize heat loss, thermal breaks, nylon washers, or insulating pads should be used. Thermal performance calculations shall comply with BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: The screw must provide high mechanical strength and corrosion resistance. Material and mechanical properties shall comply with BS EN ISO 3506 (Mechanical properties of corrosion-resistant stainless steel fasteners). Joints shall be designed in accordance with BS EN 1993-1-8 (Eurocode 3: Design of joints). For external applications, A4 stainless steel is recommended to ensure resistance to aggressive atmospheric conditions.

Fire Safety Considerations: Stainless steel is non-combustible (Class A1) according to BS EN 13501-1. When used in façade and structural systems, it does not contribute to fire spread. The screws retain part of their load-bearing capacity at elevated temperatures in accordance with BS EN 1993-1-2 (Structural fire design). Fire performance of assemblies is verified through BS EN 13501-2 and BS 8414 testing.

Design Life: The expected service life of the Stainless Steel Screw (Big) is a minimum of 30 years, provided correct installation and the use of an appropriate stainless steel grade (A4 or higher), in accordance with BS EN ISO 3506 and BS EN 1993.

Testing Regime: The screws shall be tested for:

  • Mechanical strength, shear, and pull-out resistance;

  • Corrosion resistance (BS EN ISO 9227);

  • Durability of connections and fire performance of the complete façade or structural system (BS EN 13501-2 and BS 8414)

 

F-03-01 Stainless steel screw (rail to bracket)

General Information: A stainless steel screw (rail to bracket) is a fastener specifically designed to securely fix a support rail to a bracket within ventilated façade systems. It provides structural integrity and stability, while offering resistance to environmental influences such as moisture and temperature fluctuations.

Energy / Thermal Considerations: Although the screw itself is not a thermal element, it may contribute to localised thermal bridging. To minimise heat loss, thermal break pads or isolators should be used between the bracket and the supporting structure. The thermal performance of the assembly should be assessed in accordance with BS EN ISO 10211 (thermal bridge modelling) and BS EN ISO 6946 (thermal transmittance calculations).

Technical Considerations: The screw must meet requirements for mechanical strength, pull-out resistance, and corrosion resistance. Stainless steel used should conform to BS EN 10088 (commonly A2 or A4 grades in accordance with ISO 3506). Installation must be torque-controlled to prevent deformation of the rail and to ensure a secure, long-lasting connection. Additional structural requirements are governed by BS EN 1993 (Eurocode 3) and BS EN 1090-1 (CE marking for structural components).

Fire Safety Considerations: Stainless steel is a non-combustible material and is classified as Class A1 under BS EN 13501-1. In the event of fire, the screw must maintain its mechanical performance, especially in applications involving fire-resistant façade assemblies. Its use is permitted in fire barrier systems and critical fixings, provided its temperature resistance is verified.

Design Life: The expected service life of the screw is at least 30 years, assuming the use of A4-grade stainless steel and proper installation in line with BS EN ISO 9223 (corrosivity categories) and BS EN 1991 (actions on structures). Correct specification ensures long-term durability under varying climatic conditions.

Testing Regime: Testing includes:

  • Tensile and shear strength verification to BS EN ISO 898-1 and ISO 3506;

  • Corrosion resistance via salt spray testing per BS EN ISO 9227;

  • Fire performance assessment as part of a full façade assembly in accordance with BS 8414 and BR 135 (if applicable);

  • Confirmation of non-combustibility to BS EN 13501-1 (Class A1).

 

F-03-02 Stainless steel screw (panel to rail)

General Information: The Stainless Steel Screw (Panel to Rail) is used for fixing cladding panels to rails in ventilated façade systems. It ensures a strong and durable connection between the cladding and the substructure, providing stability against service and wind loads.

Energy / Thermal Considerations: Due to the high thermal conductivity of stainless steel, screws may create localised thermal bridges. To reduce heat loss, thermal breaks or insulating pads are recommended at fixing points. Thermal performance and thermal bridge assessment are governed by BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: The screws must provide high resistance to shear, pull-out, and fatigue loads. Fasteners must comply with BS EN ISO 3506 (Corrosion-resistant stainless steel fasteners) and BS EN 14592 (Mechanical fasteners for timber constructions — applicable in hybrid systems). Stainless steel grades A2 or A4 should be selected depending on the exposure conditions. Connections must be designed in accordance with BS EN 1993-1-8 (Eurocode 3: Design of joints).

Fire Safety Considerations: Stainless steel is classified as A1 under BS EN 13501-1 and is non-combustible. Within façade systems, screws maintain loadbearing capacity up to temperature limits defined in BS EN 1993-1-2 (Structural fire design). The overall fire performance of the façade system must be verified according to BS EN 13501-2 and BS 8414.

Design Life: The expected service life of the Stainless Steel Screw (Panel to Rail) is at least 30 years, provided that corrosion-resistant stainless steel grades (e.g. A4 for external façades in aggressive environments) are used and connections are properly designed.

Testing Regime: Screws must undergo testing for mechanical strength (BS EN ISO 3506), joint durability, and corrosion resistance (BS EN ISO 9227). Ventilated façade systems, including fixings, must be tested as complete assemblies in accordance with BS EN 13830 and BS 8414.

 

F-05-01 Frame anchor (fire)

General Information: The fire-resistant frame anchor is designed for the secure fixing of metal or façade frames into building structures while meeting fire safety requirements. It ensures stability and preserves the integrity of cladding and structural elements when exposed to high temperatures.

Energy / Thermal Considerations: Anchors must withstand elevated thermal loads without loss of strength, in compliance with the fire resistance standards BS EN 1363 and BS EN 1364. These standards ensure the anchor’s performance under fire conditions, preserving its mechanical function during thermal exposure.

Technical Considerations: Specifications are defined by BS EN 845-1 and BS EN 1993 (Eurocode 3), covering aspects such as load-bearing capacity, corrosion resistance, and resistance to mechanical stresses. The anchor must demonstrate reliable performance under both static and dynamic loads.

Fire Safety Considerations: Anchors must achieve a fire resistance classification of EI30, EI60, or higher according to BS EN 13501-2, ensuring that the fixing system maintains its load-bearing and integrity functions for the specified fire exposure period.

Design Life: The expected service life of the anchor is at least 30 years, as per BS EN 845-1, assuming correct installation and routine maintenance in accordance with the manufacturer’s guidelines.

Testing Regime: Testing includes fire resistance evaluation, shear strength testing, and corrosion resistance under simulated environmental conditions to ensure compliance with safety and durability requirements.

 

G-01-01 Lightweight Steel Frame System

General Information: The LSFS – Lightweight Steel Frame System is used for load-bearing and enclosing structures in residential, commercial, and industrial buildings. It provides high strength-to-weight ratio, rapid installation, and design flexibility.

Energy / Thermal Considerations: The system shall minimise thermal bridges in compliance with BS EN ISO 10211. Additional thermal insulation materials shall be applied to meet energy efficiency standards (BS EN ISO 6946).

Technical Considerations: The structure shall conform to strength and stability requirements as per BS EN 1993-1-3 (Eurocode 3: Design of Steel Structures). Geometric and installation tolerances shall comply with BS EN 1090-2 (Execution Standards for Steel Structures).

Fire Safety Considerations: Depending on application, the system shall provide fire resistance in accordance with BS EN 13501-2. Cladding with non-combustible materials (Class A1/A2-s1,d0 per BS EN 13501-1) or application of fire-protective coatings may be utilised.

Design Life: The design service life shall be no less than 50 years, subject to compliance with corrosion protection (BS EN ISO 12944) and maintenance requirements (BS EN 1990).

Testing Regime:

Testing shall include load-bearing capacity verification (BS EN 1993-1-3), corrosion resistance (BS EN ISO 9227), and fire resistance (BS EN 1363-1).

 

G-02-01 Weather seal membrane

General Information: The weather seal membrane is a waterproof and airtight layer used in façade and window systems to protect joints and interfaces from moisture, air, and dust ingress. It is typically applied between structural components of the building envelope (e.g. between the window frame and the wall) to provide long-lasting airtight and watertight sealing.

Energy / Thermal Considerations: The membrane contributes to the required levels of air and vapour tightness in façade systems, enhancing the building's overall energy performance by reducing infiltration-related heat loss. It must comply with BS EN 12114 (air permeability of building joints) and BS EN 13984 (vapour control layers), ensuring compatibility with the insulation system and maintaining overall airtightness. Effective vapour control and sealing are essential to meeting the thermal performance criteria outlined in BS EN ISO 6946.

Technical Considerations: The membrane must exhibit high elasticity, durability, water resistance, and the ability to maintain its mechanical integrity under joint movement and deformation. In accordance with BS EN 13984 and BS EN 13859-2 (waterproofing membranes for walls and roofs), the membrane must be resistant to UV radiation, weathering, and temperature fluctuations. Compatibility with commonly used adhesives and sealants in façade assemblies is also essential.

Fire Safety Considerations: Weather seal membranes are typically classified as Class E under BS EN 13501-1. Their use is generally permitted in buildings under 18 metres in height, in line with current façade fire safety guidance and regulations. For buildings exceeding this height, membranes with a higher fire resistance classification are required.

Design Life: The expected service life of the membrane is approximately 25–30 years, provided it is correctly installed and protected from mechanical damage and prolonged UV exposure. Long-term durability and performance are supported by accelerated ageing and climate resistance testing as per BS EN 1296 and BS EN 13859-2.

Testing Regime: The membrane should be tested in accordance with the following standards:

  • BS EN 13859-2 – mechanical strength and water resistance;

  • BS EN 1928 – watertightness testing;

  • BS EN 12114 – air permeability performance;

  • BS EN 1296 – artificial ageing;

  • BS EN 13501-1 – fire classification (typically Class E).

 

G-02-02 Breather membrane

General information: The breather membrane is used as a water- and wind-resistant layer in building envelope constructions, particularly behind cladding façade systems and roofs. The membrane prevents moisture ingress from outside while allowing water vapour to escape from within the structure, preventing condensation and enhancing the durability of insulation.

Energy / Thermal considerations: In accordance with BS EN 13859-2 (walls) and BS EN 13859-1 (roofs), the membrane must have high vapour permeability and low thermal conductivity, helping to maintain the effectiveness of the insulation layer. Its use minimises heat loss by protecting insulation from moisture and draughts, in accordance with BS EN ISO 13788 for moisture control and condensation management.

Technical considerations: According to BS EN 13859, the membrane must be UV-resistant for the declared installation period, retain mechanical strength under tension and puncture, and withstand weathering. The membrane construction must resist wind loads and remain stable under temperature fluctuations. Installation should follow manufacturer guidelines for joint sealing and lap overlaps.

Fire safety considerations: In accordance with BS EN 13501-1, the membrane should have a verified reaction-to-fire classification, e.g., B-s1,d0 or higher, limiting flame spread and smoke production. When designing façades, the membrane is selected to meet the fire performance requirements of the system, taking into account BS EN 13501-2 for construction elements.

Design life: Expected design life: 30 years according to BS EN 13859, provided proper installation, protection from direct UV exposure after cladding installation, and adherence to operational requirements.

Testing regime: In accordance with BS EN 13859, the membrane is tested for water resistance, vapour permeability (Sd-value), tensile and tear strength, resistance to temperature variations, and ageing. Additionally, it is classified for fire performance according to BS EN 13501-1

 

G-02-03 Vapour control layer (VCL)

General information: The vapour control layer (VCL) is used in building envelope constructions to restrict the diffusion of water vapour from interior spaces into insulation. It is applied in façade and roof systems, preventing condensation within the construction and ensuring the durability of thermal insulation and structural elements.

Energy / Thermal considerations: In accordance with BS EN ISO 13788 and BS EN 13984, the VCL must have low vapour permeability (high Sd-value), preventing moisture from reaching the insulation. Controlling the moisture regime helps maintain the design thermal performance of the insulation and prevents a reduction in the efficiency of the thermal layer.

Technical considerations: According to BS EN 13984, the VCL must provide mechanical strength, resistance to puncture and tear, and ensure airtightness at joints and connections. Installation requires proper sealing of overlaps and the use of specialised tapes to maintain a continuous vapour barrier. The material must remain stable across the operating temperature range and be compatible with other building materials.

Fire safety considerations: In accordance with BS EN 13501-1, the VCL must have a verified reaction-to-fire classification (e.g., B-s1,d0 or higher), limiting flame spread and smoke generation. In façade and roof systems, the layer is selected to meet the fire performance requirements of the entire assembly in accordance with BS EN 13501-2.

Design life: Expected design life: 30 years according to BS EN 13984, provided correct installation and protection from mechanical damage during construction and operation.

Testing regime: In accordance with BS EN 13984, the VCL is tested for water vapour permeability (Sd-value), tensile and tear strength, and resistance to ageing and temperature effects. Additionally, the material is classified for reaction to fire according to BS EN 13501-1

 

G-02-05 Waterproofing membrane

General Information: The waterproofing membrane is designed to protect building structures from water ingress, preventing moisture damage and ensuring building durability. It is used in roofing systems, underground structures, balconies, and terraces.

Energy/Thermal Considerations: The membrane may affect the thermal performance of the structure. In some applications, it is used in combination with thermal insulation materials, complying with BS EN 13967 requirements for flexibility and resistance to thermal deformation.

Technical Considerations: The membrane shall possess high tensile strength, puncture resistance, and UV stability (for external applications). It must conform to BS EN 13707 (for roofing membranes) and BS EN 13970 (for waterproofing under screeds).

Fire Safety Considerations: Depending on application, the membrane shall meet relevant fire safety classifications, such as BROOF(t4) per BS EN 13501-5 (for roofing materials). Internal membranes may require a minimum fire reaction class of B-s1,d0 (BS EN 13501-1).

Design Life: The expected service life ranges from 20 to 50 years depending on membrane type and operating conditions, in accordance with BS EN 13967 guidelines.

Testing Regime:

Testing includes water tightness verification (BS EN 1928), resistance to static and dynamic water exposure (BS EN 13583), and mechanical strength assessment (BS EN 12311).

 

G-03-01 Non-combustible sheathing board (for LSFS)

General Information: The non-combustible cladding panel (for LSFS) serves as a protective and structural layer in Lightweight steel frame systems (LSFS), providing fire resistance, mechanical stability, and additional thermal insulation.

Energy / Thermal Considerations: The panel shall comply with thermal conductivity and energy efficiency requirements per BS EN ISO 6946. It may be used in conjunction with insulation materials to enhance the thermal performance of building envelopes.

Technical Considerations: The material shall possess high compressive strength and deformation resistance, conforming to BS EN 13950 (gypsum-based boards) or BS EN 15283 (cement/fibre-based boards). Permissible geometric and flatness tolerances shall be regulated by BS EN 520.

Fire Safety Considerations: The panel shall be classified as non-combustible (A1 or A2-s1,d0 per BS EN 13501-1) and provide fire resistance in accordance with BS EN 1364-1 (fire resistance testing for non-load-bearing elements).

Design Life: The expected service life shall be no less than 30 years, subject to proper installation and maintenance conditions.

Testing Regime: Testing shall include:

  • Fire resistance (BS EN 1364-1)

  • Mechanical strength (BS EN 520)

  • Moisture and frost resistance (where applicable) as per relevant standards.

 

G-04-01 Mineral wool insulation (for external application) (k ≤ 0.035 W/mK)

General Information: Mineral wool insulation (for wall) is used in external and internal building envelopes to provide thermal, acoustic and fire insulation. Installed in multi-layer walls, façade systems or framed partitions as a non-combustible insulation material.

Energy/Thermal Considerations: Mineral wool features low thermal conductivity (λ ≈ 0.032-0.040 W/m·K), complying with BS EN 13162 - the standard for thermal insulation products for buildings. It effectively reduces heat loss and helps building envelopes meet energy efficiency requirements (e.g. BS EN ISO 6946). Insulation thickness is selected based on required U-value.

Technical Considerations: According to BS EN 13162, mineral wool must maintain dimensional stability, moisture resistance, compressive strength (when used in rainscreen systems), and long-term durability. The material must retain its insulating properties under humid conditions. For walls, compliance with strength classes and dimensional stability under temperature fluctuations is essential. Capillary activity and water vapour diffusion resistance (µ-factor) are also considered.

Fire Safety Considerations: Mineral wool is a non-combustible material typically classified as A1 per BS EN 13501-1 - it doesn't support combustion, emit toxic gases or produce flaming droplets. Used as a component in fire protection systems for façades, partitions and fire compartments. When used in external insulation systems (e.g. ventilated façades), it ensures structural fire safety.

Design Life: The expected service life of mineral wool is minimum 30 years per BS EN 13162, provided proper installation, moisture protection and avoidance of mechanical damage.

Testing Regime: Testing is conducted according to BS EN 13162 and BS EN 1602-1609, including determination of thermal conductivity, water absorption, compressive strength, ageing resistance and dimensional stability. Fire performance is verified per BS EN 13501-1.

 

G-04-02 Mineral wool insulation (to void between LSFS studs) (k ≤ 0.038 W/mK)

General Information: Mineral wool insulation (for LSF) is a mineral fibre insulation material used in light steel framing (LSF) constructions. It provides thermal and acoustic insulation for external and internal walls, floors, partitions, and roofing systems. Installed between steel studs, it ensures the required thermal and acoustic performance of building envelopes.

Energy / Thermal Considerations: Mineral wool has low thermal conductivity (λ ≈ 0.032–0.040 W/m·K), complying with BS EN ISO 10456 and BS EN 13162 (thermal insulation products - mineral wool products). In LSF systems, its use improves thermal resistance (R-value) and reduces heat loss through walls and roofs. The insulation must retain its thermal performance over its service life, including resistance to slumping and sagging. Thermal efficiency calculations follow BS EN ISO 6946 (thermal performance of building components) and BS EN ISO 10211 (thermal bridges).

Technical Considerations: Mineral wool for framed systems must exhibit sufficient rigidity, dimensional stability, water repellence, and vapour permeability. Per BS EN 13162, it must be classified by:

  • Density

  • Compressive/tensile strength

  • Fibre length

  • Other mechanical properties Additionally, resistance to vibration and vertical structural loads must be considered.

Fire Safety Considerations: Mineral wool is classified as a non-combustible material (A1 per BS EN 13501-1), meaning it does not contribute to fire, smoke, or flaming droplets. This makes it highly effective in LSF walls, where fire resistance (BS EN 1364-1 – non-load-bearing walls) is required. When combined with appropriate cladding, it can achieve EI 30–120 fire resistance ratings.

Design Life: The expected service life is minimum 50 years (BS EN 13162), provided the insulation is:

  • Protected from moisture ingress

  • Not mechanically damaged

  • Properly installed to prevent settling in vertical applications

Testing Regime: Testing includes:

  • BS EN 13162 (product characteristics)

  • BS EN 1604 (dimensional stability & shrinkage resistance)

  • BS EN 1607 (tensile strength)

  • BS EN 12667 (thermal conductivity)

  • BS EN ISO 1182 & BS EN 13501-1 (reaction to fire)

  • Full LSF system fire testing (BS EN 1364-1) may also be required.

 

H-02-01 Double glazed unit (DGU-1)

General Information: A double glazed unit (DGU) is used in window, door, and façade systems to provide thermal and acoustic insulation. It consists of two glass panes separated by a spacer frame with a hermetically sealed cavity, which may be filled with air or an inert gas (e.g., argon). DGUs are employed in residential, commercial, and industrial buildings to enhance energy efficiency and comfort.

Energy / Thermal Considerations: According to BS EN 1279 (standards for insulating glass units), a double glazed unit must achieve a low thermal transmittance (U-value), particularly when using low-emissivity coatings (Low-E) and gas filling. This ensures compliance with building energy efficiency requirements, as specified in BS EN ISO 10077-1 and BS EN ISO 10456. The use of inert gases and warm-edge spacer bars further reduces heat loss and the risk of condensation.

Technical Considerations: Technical requirements for double glazed units are defined by BS EN 1279 (Parts 1–6), covering durability, airtightness, moisture absorption, optical properties, and thickness tolerances. Additional parameters include sound insulation, wind load resistance, and impact resistance (where required). Compatibility with window or façade systems must be ensured in accordance with BS EN 14351-1 (windows and external pedestrian doors).

Fire Safety Considerations: Standard double glazed units made from tempered or float glass are not fire-resistant, though they may be used in non-fire-rated barriers. Their behaviour in fire depends on the glass type: standard glass is not classified under BS EN 13501-1, but tempered or laminated glass may meet certain safe breakage requirements. If the glazed unit is part of a fire-rated system, specialist fire-resistant glass certified to BS EN 14449 and BS EN 13501-2 must be used.

Design Life The expected service life of a double glazed unit is at least 25–30 years, assuming proper installation and sealing quality, as per BS EN 1279-2 and -3.

Testing Regime: Testing includes assessments for:

  • Airtightness (BS EN 1279-2)

  • Moisture absorption (BS EN 1279-3)

  • Thermal transmittance (BS EN 674)

  • Light transmittance (BS EN 410)

  • Sound insulation (BS EN ISO 10140)

  • Resistance to climatic cycling and ageing

  • Full-scale testing of glazed units within window systems is conducted under BS EN 14351-1.

 

H-03-01 Single glazed unit (SGU-1)

General information: A Single Glazed Unit is used in window and façade constructions as a basic glazing option. It consists of a single pane of glass without additional cavities and is primarily used for internal partitions, unheated spaces, or buildings with low thermal insulation requirements.

Energy / Thermal considerations: Single glazing has a high U-value, limiting its suitability for modern energy-efficient buildings. It does not meet energy performance requirements according to BS EN ISO 10077 and BS EN ISO 6946 for external building elements, but may be used in areas where thermal performance is not critical.

Technical considerations: The glass must provide sufficient strength to resist wind and service loads, in accordance with BS EN 12150 (thermally toughened glass), BS EN 12600 (pendulum impact testing), and, where required, BS EN 14449 (laminated glass). Sealing and mechanical fixing should ensure long-term durability, although single glazing does not provide the additional insulation of an insulating glass unit.

Fire safety considerations: Glass is a non-combustible material and classified as A1 under BS EN 13501-1. Standard single glazing is not fire-resistant; for fire-rated partitions, special fire-resistant glass certified to BS EN 13501-2 may be used.

Design life: The expected service life of a Single Glazed Unit is 25–30 years, provided the use of safe glass in accordance with BS EN 12150 and BS EN 14449, and correct installation with protection against mechanical damage.

Testing regime: Single Glazed Units should be tested for mechanical strength (BS EN 12150, BS EN 12600), light transmission and solar properties (BS EN 410), and resilience to climatic exposure where used externally.

 

I-01-02 Aluminium panel (t-3mm)

General Information: The Aluminium Panel (3 mm thick) is used in ventilated façade systems as an external cladding material. It protects the building from environmental exposure, defines the architectural appearance, and provides a lightweight, durable and corrosion-resistant façade finish.

Energy / Thermal Considerations: Aluminium panels have high thermal conductivity; therefore, they are typically used as part of a ventilated façade assembly, where the thermal performance depends on the insulation layer and the rear ventilation cavity. The panel must contribute to the overall thermal behaviour of the envelope in accordance with BS EN ISO 6946 and BS EN ISO 10077-1 (as part of the assembly). Surface finishes and colours may affect solar absorption and overheating, which must be assessed in accordance with BS EN 410.

Technical Considerations: A 3 mm aluminium panel must provide sufficient strength and stiffness to resist wind loads and service conditions. Material requirements for aluminium sheet are defined in BS EN 485 and BS EN 573 (Aluminium and aluminium alloys). Structural performance and design must follow BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures). Panels shall be protected with anodising or powder coating in accordance with BS EN 12206 or BS EN 12373-1 to ensure resistance to corrosion and atmospheric exposure.

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and is non-combustible. However, the fire performance of the façade system is governed by the combined behaviour of the cladding panel, supporting substructure and insulation. When incorporated into the façade assembly, the system must comply with BS EN 13501-2 and undergo full-scale system testing in accordance with BS 8414 to verify façade fire performance.

Design Life: The expected service life of the Aluminium Panel (t-3 mm) is at least 30 years, provided correct installation, durable protective coatings and appropriate maintenance are ensured, in accordance with BS EN 1999 and BS EN 12206.

Testing Regime: Panels shall be tested for mechanical strength, bending performance and flatness in accordance with BS EN 485-4, and for corrosion resistance in accordance with BS EN ISO 9227. Coatings shall be tested for adhesion, UV resistance and atmospheric durability in accordance with BS EN 12206 and BS EN 13523. When forming part of a façade system, the panel participates in fire performance assessment in accordance with BS EN 13501-1 and BS 8414

 

I-01-05 Aluminium curve panel (t-2mm)

General Information: The Aluminium Curve Panel (2 mm thick) is used in ventilated façade systems to create curved surfaces and architecturally expressive elements. The panel provides a lightweight, aesthetically refined external envelope with high resistance to atmospheric exposure while maintaining low mass and excellent corrosion resistance.

Energy / Thermal Considerations: Due to the high thermal conductivity of aluminium, the thermal behaviour of the façade is primarily governed by the insulation layer and the configuration of the ventilated cavity rather than the 2 mm panel itself. The curved geometry may create complex junctions where localised thermal bridging can occur; these must be addressed through proper detailing and installation in accordance with BS EN ISO 10211 and BS EN ISO 6946. Optical properties of the applied coating (solar absorption and reflectance) shall comply with BS EN 410.

Technical Considerations: Curved panels with a thickness of 2 mm must provide sufficient strength, stiffness and geometric stability under wind actions and service loads. Material properties shall comply with BS EN 485, BS EN 573 and BS EN 515 (Aluminium and aluminium alloys). Forming processes for curved elements shall maintain mechanical integrity and meet dimensional tolerances in accordance with BS EN 1090-3. Protective finishes such as anodising or powder coating shall be applied in accordance with BS EN 12206 or BS EN 12373-1 to ensure durability and corrosion resistance.

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and does not contribute to fire loads or produce combustible gases. However, the fire resistance of the façade system depends on the combined behaviour of the cladding, substructure and insulation. When the panel is used within a ventilated façade assembly, the system must comply with BS EN 13501-2 and be verified through full-scale testing in accordance with BS 8414.

Design Life: The expected service life of the Aluminium Curve Panel (t-2 mm) is at least 30 years, provided appropriate protective coatings are applied, installation requirements are followed, and regular maintenance is carried out, in line with BS EN 1999 and BS EN 12206.

Testing Regime: Panels shall undergo testing for mechanical strength, deformation resistance and shape stability in accordance with BS EN 485-4. Coatings shall be tested for weather resistance, adhesion and UV stability in accordance with BS EN 12206 and the BS EN 13523 series. As part of a façade system, the panel must be included in fire performance assessments in accordance with BS EN 13501-1 and BS 8414. 

J-01-01 Aluminium flashing

General Information: Aluminium flashing is a supplementary element used to protect façade and roofing junctions from water ingress and to provide a clean, finished appearance at connection points. It is typically installed at panel joints, window and door perimeters, roof edges, and other envelope transitions.

Energy / Thermal Considerations: Due to the high thermal conductivity of aluminium, flashing can act as a point thermal bridge. To reduce unwanted heat loss, the use of gaskets, sealing membranes, or thermal breaks at the interface with warm interior zones is recommended. The thermal impact of flashing elements should be assessed using BS EN ISO 10211 (thermal bridge analysis) and BS EN ISO 6946 (thermal transmittance calculation).

Technical Considerations: Flashing is fabricated from aluminium or aluminium alloy in accordance with BS EN 485 and BS EN 573. It must have adequate rigidity, be resistant to corrosion, and withstand exposure to UV radiation and weathering. Surface protection is typically achieved via anodising or polyester powder coating, in compliance with BS EN 12206. Proper installation must ensure water-tightness and effective water drainage. Dimensions and profiles are project-specific and must align with design details for junctions.

Fire Safety Considerations: Aluminium is a non-combustible material with a reaction to fire classification of Class A1 according to BS EN 13501-1. However, it loses mechanical strength when exposed to temperatures above 300–400 °C. Therefore, its use in fire-rated zones must be verified through system-level fire testing as per BS 8414 or BS EN 1364, when flashing forms part of a critical fire protection detail.

Design Life: The expected design life of aluminium flashing is at least 30 years, provided corrosion-resistant alloys and appropriate protective coatings are used. Durability is supported by compliance with BS EN 1999 (Eurocode 9) and BS EN 1090-1. Regular inspection and maintenance are essential to ensure long-term performance.

Testing Regime: Testing procedures include:

  • Corrosion resistance via salt spray testing in accordance with BS EN ISO 9227;

  • Water tightness and sealing efficiency as part of the installed façade system;

  • Fire reaction classification per BS EN 13501-1 (Class A1);

  • Fire performance testing per BS 8414, if flashing is included in fire-critical assembly.

J-02-01 Aluminium sill (t-2mm)

General information: An aluminium sill (2 mm thick) is a horizontal element installed at window or façade openings, designed to direct rainwater and meltwater away from the wall surface and to protect the lower part of the opening from moisture ingress and mechanical damage. It is used in both ventilated façade systems and window assemblies, and is mounted beneath the window frame.

Energy / Thermal considerations: Although aluminium sills do not possess intrinsic thermal insulation properties, their design must address the minimisation of thermal bridging, particularly at the junction with the window frame. During the design stage, thermal break pads or installation over an insulated layer should be considered to maintain the required thermal resistance of the detail in accordance with BS EN ISO 6946 and BS EN ISO 10211 (thermal bridge analysis). It is also essential to ensure airtight and watertight joints to prevent air and moisture infiltration.

Technical considerations: A 2 mm thick aluminium sill must demonstrate resistance to mechanical loads, deformation, and environmental exposure. Compliance with BS EN 485 (mechanical properties of wrought aluminium), BS EN 573 (chemical composition), and BS EN 15088 (aluminium products for structural applications) ensures the quality and performance of the material. The aluminium should be provided with a protective finish, such as anodising or powder coating, in accordance with BS EN 12206 (organic coatings) to enhance resistance to corrosion and UV degradation.

Fire safety considerations: Aluminium is classified as a non-combustible material (Class A1 under BS EN 13501-1). It does not sustain combustion, emit toxic fumes, or produce flaming droplets, making it a safe component in systems requiring fire resistance, particularly in external zones and escape routes. However, when used in conjunction with sealants or gaskets, the fire classification of these additional materials must also be taken into account.

Design life: The expected service life of an aluminium sill is at least 40–50 years, provided proper usage conditions are maintained and the protective coating is intact. This aligns with typical service life expectations for aluminium components used in façade and window systems, as referenced in BS EN 1999-1-1 (Eurocode 9 — design of aluminium structures).

Testing regime: Testing may include assessment of corrosion resistance (BS EN ISO 9227 — salt spray testing), mechanical strength (including bending and impact resistance), coating adhesion (BS EN ISO 2409), and drainage performance as part of the window or façade assembly, in accordance with BS EN 1027 (water tightness) and BS EN 12208 (watertightness of windows and doors).

 

J-03-01 Aluminium reveal

General Information: An aluminium reveal is a supplementary façade component used to finish window and door openings within cladding systems. It provides a clean and durable aesthetic transition between the façade and frame, protects structural components from environmental exposure, and may serve a secondary function in water drainage away from the window or door assembly.

Energy / Thermal Considerations: Although the aluminium reveal itself is not a thermal insulator, its design and installation must minimise thermal bridging, particularly at junctions with insulated façade elements. The use of thermal breaks, insulated backing strips, or compression gaskets is recommended to improve performance. Thermal transmittance of junction details should be assessed using BS EN ISO 10211, and overall façade performance calculated in accordance with BS EN ISO 6946.

Technical Considerations: The reveal must be fabricated from aluminium that complies with BS EN 485 (rolled products), BS EN 515 (temper designation), and BS EN 573-3 (alloy designation). It must resist deformation, UV exposure, discolouration, corrosion, and mechanical impact. Coating durability should meet BS EN 12206 (for powder-coated or anodised finishes). Proper integration with window frames and cladding panels is essential to prevent moisture ingress and maintain airtightness.

Fire Safety Considerations: Solid aluminium is a non-combustible material and is classified as Class A1 under BS EN 13501-1. However, as part of the window or door assembly in high-rise buildings (18m+), the reveal must be used within a façade system that meets the fire performance requirements of BS 8414 and BR 135. Care should be taken to ensure that no combustible materials are used in adjacent sealing or backing components.

Design Life: The expected service life of an aluminium reveal is 30 years or more, provided it is correctly installed, protected against galvanic corrosion (particularly at junctions with dissimilar metals), and maintained in accordance with manufacturer guidance. Design should comply with BS EN 1999 (Eurocode 9 – Aluminium Structures).

Testing Regime: Typical performance testing includes:

  • BS EN ISO 6892-1 – Tensile properties of aluminium

  • BS EN 12206 – Coating durability and weathering resistance

  • BS EN ISO 9227 – Corrosion resistance via salt spray testing

  • BS EN 13501-1 – Reaction to fire (A1 classification)

  • BS 8414 – Fire performance of the complete façade system (where required for buildings >18m)

 

J-05-01 Aluminium sheet (t-2mm)

General Information: Aluminium Sheet with a thickness of 2 mm is used in construction for façade cladding, ventilated systems, and as part of substructures. It is characterised by low weight, corrosion resistance, and high workability during fabrication and installation.

Energy / Thermal Considerations: Aluminium has high thermal conductivity and does not provide insulation. When applied in façade systems, it must be combined with thermal insulation materials. The influence of thermal bridges and the coefficient of linear thermal expansion must be taken into account, in accordance with BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: Aluminium sheet (2 mm thick) must comply with BS EN 485 (Aluminium and aluminium alloys – Sheet, strip and plate) and BS EN 573 (Chemical composition and form of wrought aluminium alloys). Strength and durability are ensured through alloys defined in BS EN 485-2. When designing façades with aluminium sheets, BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures) must be followed. For corrosion protection, anodising (BS EN 12373) or powder coating (BS EN 12206) is applied.

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and is non-combustible. In façade systems, it does not contribute to fire spread. The fire performance of the complete system must be verified through testing in accordance with BS EN 13501-2 and BS 8414.

Design Life: The expected service life of Aluminium Sheet (t = 2 mm) is at least 30 years when suitable protective finishes are applied and correct design principles are followed, in accordance with BS EN 1999-1-1 and BS EN 485.

Testing Regime: Sheets must undergo testing for mechanical properties (strength, stiffness, impact resistance) in accordance with BS EN 485-2, as well as corrosion resistance testing under BS EN ISO 9227. Within façade systems, aluminium panels must be fire tested in accordance with BS EN 13501-1/2 and BS 8414.

 

J-11-01 Aluminium sheet with perforation (t-2mm)

General Information: The 2 mm thick perforated aluminium sheet is used in construction for façade cladding, sun-shading screens, ventilation grilles, acoustic panels, and decorative elements, combining both functional and architectural purposes.

Energy / Thermal Considerations: In accordance with BS EN ISO 10077 and BS EN ISO 6946, perforated aluminium panels can serve as sun-shading and ventilation elements, reducing the building’s thermal load by controlling solar radiation and providing natural ventilation. When integrated into façade systems, thermal bridging and compatibility with insulation layers must be considered.

Technical Considerations: Aluminium sheets must comply with BS EN 485 (aluminium and aluminium alloy sheet and strip), BS EN 515 (temper designation), and BS EN 573 (chemical composition of aluminium alloys). Perforations must be designed to meet strength and stiffness requirements in accordance with BS EN 1999 (Eurocode 9 — design of aluminium structures). The assembly must withstand wind loads and service conditions.

Fire Safety Considerations: According to BS EN 13501-1, aluminium is classified as A1 (non-combustible), ensuring no contribution to fire development. However, where coatings or paint systems are applied, their fire classification must be verified, with a minimum of A2-s1,d0.

Design Life: The expected service life of the perforated aluminium sheet is at least 30 years, provided the correct alloy is selected and corrosion protection is applied in accordance with BS EN 485 and BS EN 12206 (anodising and powder coating).

Testing Regime: Testing must be carried out in accordance with BS EN 485 (dimensional and mechanical properties), BS EN ISO 6892 (tensile testing of metals), and BS EN 12206 (coating quality). For façade applications, additional testing is carried out in accordance with BS EN 13830 (building envelope façade systems).

 

K-01-02 Aluminium Z-profile

General information: Aluminium Z-profiles are used as structural or fixing elements in façade, roofing and wall systems to connect and secure panels, cladding, and other building components. They provide installation accuracy, structural stability, and facilitate the assembly of modular elements.

Energy / Thermal considerations: According to BS EN ISO 6946 (Thermal performance of building components) and BS EN ISO 10077 (Thermal performance of windows, doors and shutters), aluminium Z-profiles have high thermal conductivity and can create thermal bridges. To minimise energy loss, it is recommended to use thermal breaks or insulating inserts between the profile and the façade elements.

Technical considerations: In accordance with BS EN 485 and BS EN 573 (Aluminium and aluminium alloys), Z-profiles must have sufficient strength, rigidity, and resistance to deformation under installation and service loads. The profile should be corrosion-resistant and compatible with other construction elements. Additionally, mounting holes and profile dimensions must meet design requirements to ensure reliable panel attachment.

Fire safety considerations: According to BS EN 13501-1, aluminium is non-combustible (A1). However, the profile may come into contact with combustible façade components, so the design should account for compatibility with fire-protective materials to comply with Approved Document B and ensure the fire safety of the façade system.

Design life: In accordance with BS EN 1999 (Eurocode 9: Design of aluminium structures) and BS EN 485, the expected service life of an aluminium Z-profile is at least 30 years, provided it is correctly designed, installed, and protected against corrosion.

Testing regime: Testing of aluminium Z-profiles is conducted according to BS EN 573 and BS EN 755 (Aluminium and aluminium alloys – Extruded rod/bar, tube and profiles) for strength, rigidity, and corrosion resistance. Additional checks may include compatibility with façade systems and compliance with thermal bridge requirements in accordance with BS EN ISO 10077.

 

K-01-04 Aluminium angle (for cladding)

General information: The aluminium angle profile is employed in ventilated façade systems for the fixing, connection, and reinforcement of cladding panels, as well as for the formation of corner and joint details, ensuring precise alignment and structural stability.

Energy / Thermal considerations: From a thermal performance standpoint, the angle profile must be designed to minimise thermal bridging and comply with the requirements of BS EN ISO 10211, which governs the assessment of thermal bridges in building façades.

Technical considerations: Technical requirements are defined by BS EN 755 (for extruded aluminium profiles) and BS EN 1999 (Eurocode 9), covering dimensional tolerances, mechanical strength, flexural resistance, and durability under external influences.

Fire safety considerations: In terms of fire safety, the aluminium angle profile must be classified as A1 in accordance with BS EN 13501-1, confirming its non-combustibility.

Design life: The expected service life is not less than 30 years, subject to correct installation and protection from aggressive environmental conditions, as specified in BS EN 1090 and BS EN 1999. Testing procedures may include verification of dimensional accuracy, mechanical strength, and corrosion resistance under operational conditions.

 

K-01-08 Aluminium strip

General Information: The Aluminium Strip is used in façade and structural systems as an auxiliary profile for alignment, fixing, joint formation, or local reinforcement of substructure components. Due to its low thickness and the high precision of the extrusion process, the element is suitable for installation in narrow interface zones and locations where minimal additional weight is required.

Energy / Thermal Considerations: Aluminium strips exhibit high thermal conductivity, which necessitates careful consideration of potential thermal bridging within the assembly. Where the strip connects external and internal components, thermal isolators or thermal breaks should be incorporated in accordance with BS EN ISO 10211 and BS EN ISO 6946. If the strip is used externally, the optical properties of any applied coating (solar absorption and reflection) shall comply with BS EN 410.

Technical Considerations: The extruded aluminium profile shall comply with BS EN 755 and BS EN 12020 (Aluminium and aluminium alloys — Extruded profiles), ensuring accuracy of geometry, dimensional stability and material uniformity. Mechanical performance and structural capacity shall be evaluated in accordance with BS EN 1999-1-1 (Eurocode 9). For external applications, the strip shall be protected by anodising or powder coating in accordance with BS EN 12206 or BS EN 12373-1 to ensure corrosion resistance and durability.

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and does not support combustion. However, within a façade system, the fire performance of the strip must be assessed as part of the overall assembly—including insulation and substructure—and validated through system testing in accordance with BS EN 13501-2 and BS 8414.

Design Life: The expected service life of the Aluminium Strip (Extruded Elements) is not less than 30 years, provided correct installation practices are followed, protective coatings are applied, and routine maintenance is performed, in line with BS EN 1999 and BS EN 12206.

Testing Regime: The strip shall be tested for dimensional accuracy, mechanical strength, corrosion resistance, and coating stability in accordance with BS EN 755-2, BS EN ISO 9227 and the BS EN 13523 series. As part of a façade system, the element shall be included in fire performance testing to BS EN 13501-1 and BS 8414

 

K-01-10 Aluminium profile

General Information: The Aluminium Profile is used in façade, interior, and structural systems as a versatile mounting or connecting element. The profile is suitable for forming rigid frames, securing cladding, supporting substructures, and ensuring precise positioning of elements due to the high geometric stability of the extrusion.

Energy / Thermal Considerations: Aluminium has high thermal conductivity, which can lead to thermal bridging in assemblies. When used in building envelope constructions, thermal breaks, insulating pads, or separation inserts should be incorporated in accordance with BS EN ISO 10211 and BS EN ISO 6946. For external applications, the effect of surface coatings on solar absorption must be considered in accordance with BS EN 410.

Technical Considerations: The extruded aluminium profile shall comply with BS EN 755 and BS EN 12020 (Aluminium and aluminium alloys — Extruded profiles), ensuring geometric accuracy, mechanical strength, and material uniformity. Structural calculations shall be performed according to BS EN 1999-1-1 (Eurocode 9). For external applications, the profile shall be protected by anodising or powder coating in accordance with BS EN 12206 or BS EN 12373-1. The profile must withstand mechanical loads, including bending and torsion, without loss of shape.

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and is non-combustible. Within a façade system, fire performance depends on the behaviour of the complete assembly, and where required, compliance shall be verified according to BS EN 13501-2 and system tests to BS 8414. The profile does not promote flame spread, though it loses mechanical strength at high temperatures, which must be considered in joint and connection design.

Design Life: The expected service life of the Aluminium Profile (Extruded Elements) is not less than 30 years, provided corrosion protection requirements are observed, durable coatings are applied, and installation is performed correctly, in accordance with BS EN 1999 and BS EN 12206.

Testing Regime: The profile shall be tested for dimensional accuracy, mechanical strength, corrosion resistance, and coating durability in accordance with BS EN 755-2, BS EN ISO 9227, and the BS EN 13523 series. When used in façade or structural systems, the element shall be included in fire performance testing according to BS EN 13501-1 and BS 8414

 

K-02-01 Stainless steel angle

General Information: A stainless steel angle is an L-shaped profile used in façade and building systems for fastening, supporting, and connecting various components, including brackets, rails, and cladding panels. It is employed in primary and secondary connections, providing rigidity, stability, and accurate positioning of structural elements.

Energy / Thermal Considerations: Stainless steel angles can create thermal bridges where they intersect insulation. To reduce heat loss, it is recommended to use thermal break pads or insulating inserts and to perform thermal analysis of connections in accordance with BS EN ISO 10211 and BS EN ISO 6946, ensuring compliance with the energy efficiency requirements of Building Regulations Part L.

Technical Considerations: Angles must be fabricated from stainless steel in accordance with BS EN 10088 (grades AISI 304 or 316, depending on the corrosion exposure category per BS EN ISO 9223). The product must comply with BS EN 1090-1 (assessment of conformity of steel structures) and be designed in accordance with BS EN 1993-1-1 and BS EN 1993-1-8 (Eurocode 3: design of steel structures and connections). Profile dimensions and thickness are selected based on structural capacity and wind load calculations. Fasteners should comply with BS EN ISO 3506-1 / -2.

Fire Safety Considerations: Stainless steel is non-combustible with a reaction-to-fire classification of A1 under BS EN 13501-1. The angles do not contribute to flame spread or smoke production. For buildings over 18 m, angles may be used provided the complete façade system has been fire-tested in accordance with BS 8414 and assessed to BR 135.

Design Life: The expected service life of stainless steel angles is at least 60 years, given correct selection of stainless steel grade and operating conditions, in accordance with BS EN ISO 9223 and BS EN 1993 (Eurocode 3).

Testing Regime: Testing includes:

  • BS EN 10088 (chemical composition and properties of stainless steel);

  • BS EN 1090-1 (assessment of conformity of steel structures);

  • BS EN ISO 6892-1 (tensile strength and yield limit testing);

  • BS EN ISO 9227 (corrosion resistance testing — salt spray);

  • BS EN ISO 3506-1 / -2 (mechanical properties of stainless steel fasteners);

  • BS EN 13501-1 (reaction to fire — classification A1);

  • BS 8414 and BR 135 (façade system fire performance, if applicable)

 

K-02-05 Stainless steel U-profile

General Information: The Stainless Steel U-profile is used in façade, structural, and substructure applications as a load-bearing, guiding, or reinforcing element. It is suitable for securing cladding panels, supporting substructures, forming rigid frames, and providing accurate installation lines, ensuring high mechanical strength and resistance to stress.

Energy / Thermal Considerations: Stainless steel has high thermal conductivity, so when used in building envelopes, the potential for thermal bridging must be considered. To minimise heat loss, insulating pads, thermal breaks, or separation elements should be applied in accordance with BS EN ISO 10211 and BS EN ISO 6946. For external applications, solar heat gain effects should also be considered in accordance with BS EN 410.

Technical Considerations: The profile shall comply with BS EN 10088 and BS EN ISO 3506 (Mechanical properties of corrosion-resistant stainless steel). The U-profile must have high rigidity against bending and torsion, ensuring subsystem stability under wind and operational loads. Load-bearing calculations shall be performed in accordance with BS EN 1993-1-1 and BS EN 1993-1-8 (Eurocode 3). Stainless steel must provide corrosion resistance, particularly in aggressive environments, as verified according to BS EN ISO 9227.

Fire Safety Considerations: Stainless steel is classified as A1 under BS EN 13501-1 and is non-combustible. Within a façade system, the performance of the profile is assessed together with other components according to BS EN 13501-2. Subsystems using U-profiles must, where required, verify fire performance via system tests in accordance with BS 8414. Stainless steel retains part of its load-bearing capacity at elevated temperatures, as considered in BS EN 1993-1-2 (structural fire design).

Design Life: The expected service life of the Stainless Steel U-profile is at least 30 years, provided correct installation, use of a stainless steel grade with appropriate corrosion resistance (e.g., A4), and regular maintenance, in accordance with BS EN 1993 and BS EN ISO 3506.

Testing Regime: The profile shall be tested for mechanical strength, corrosion resistance, geometric accuracy, and surface stability in accordance with BS EN 10088, BS EN ISO 3506, and BS EN ISO 9227. Within a façade system, the element shall participate in fire performance tests according to BS EN 13501-1 and BS 8414

 

L-01-01 Internal wall finish

General information: Internal wall finish is applied to provide interior surfaces with the required functional and decorative properties. Depending on the design specification, this may include plaster, plasterboard sheets, cladding panels, or paint. Internal finishes ensure surface smoothness, substrate protection, and an aesthetically pleasing interior appearance.

Energy / Thermal considerations: According to BS EN ISO 13788 and BS EN ISO 6946, internal finishes influence the vapour permeability of the building envelope and, to a lesser extent, the thermal performance of the wall. When used as part of insulated wall systems, consideration must be given to the finish’s ability to regulate moisture conditions, preventing condensation and maintaining the calculated thermal resistance.

Technical considerations: In accordance with BS EN 13914 (plastering), BS EN 520 (plasterboards), and BS EN 15102 (wallcoverings and panels), internal finishes must provide adequate adhesion to the substrate, resistance to mechanical damage, abrasion resistance, and hygienic performance. Installation should comply with relevant standards, ensuring quality control of joints and surface flatness.

Fire safety considerations: According to BS EN 13501-1, finishing materials are classified by reaction to fire. Mineral plasters and plasterboards are generally classified as A1 or A2 (non-combustible), whereas decorative coatings (paints, panels) may fall into lower classes such as B or C. Design must also consider BS EN 13501-2 requirements to achieve the necessary fire resistance of the wall system as a whole.

Design life: Expected design life: 20–30 years according to BS EN 13914 and BS EN 520, provided correct installation and regular maintenance are carried out. Service life depends on the type of finish, operating conditions, and the intensity of mechanical impact.

Testing regime: According to BS EN 520 and BS EN 15102, finishes are tested for flexural strength (for sheet materials), adhesion to substrate, abrasion resistance, and resistance to moisture and temperature variations. Additional classification is carried out for reaction to fire in accordance with BS EN 13501-1.

 

L-01-02 Floor build up(internal)

General information: Internal floor build-up represents the structural layers of a floor within a building, including the substrate, insulation, leveling, and finishing layers. It provides strength, durability, sound and thermal insulation, and serves as a base for floor coverings in residential and commercial spaces.

Energy / Thermal considerations: According to BS EN ISO 6946 (Thermal performance of building components) and BS EN ISO 10211 (Thermal bridges in building construction), the internal floor “sandwich” must minimise heat loss and thermal bridging. Insulation materials used (mineral wool, expanded polystyrene, PIR, etc.) are selected to achieve regulatory thermal resistance and maintain the energy efficiency of the space.

Technical considerations: In accordance with BS EN 1264 (Heating systems in buildings – Embedded water heating systems) and BS EN 13813 (Screed material and floor screeds – Properties and requirements), the floor construction must be designed for operational loads, durability, and compatibility with building services (e.g., underfloor heating). Materials should provide sufficient strength, moisture resistance, minimal deformation, and stability against shrinkage.

Fire safety considerations: According to BS EN 13501-1, floor materials are classified by reaction to fire. Insulation and floor layers must demonstrate appropriate non-combustibility or limited combustibility (e.g., A1 or A2-s1,d0) to ensure occupant safety and prevent fire spread through internal floor structures.

Design life: In accordance with BS EN 13813 and BS EN ISO 15686 (Buildings and constructed assets – Service life planning), the expected service life of an internal floor is at least 30 years when properly designed, installed, and maintained, including timely servicing and moisture protection.

Testing regime: Testing of internal floor build-ups is carried out according to BS EN 13813 (strength and wear resistance of screed), BS EN 1264 (compatibility with embedded water heating systems), BS EN 13501-1 (fire performance and reaction to fire), and BS EN 1307 (classification of floor coverings for durability and wear resistance).

 

L-01-03 Ceiling build up(internal)

General information: Internal ceiling build-up represents the structural layers of a ceiling within a room, including the supporting framework, acoustic and thermal insulation layers, and the finishing surface. It provides acoustic comfort, thermal insulation, aesthetic finishing, and protection of structural elements from external influences.

Energy / Thermal considerations: According to BS EN ISO 6946 (Thermal performance of building components) and BS EN ISO 10211 (Thermal bridges in building construction), internal ceiling constructions should help reduce heat loss and minimise thermal bridges. Insulation materials such as mineral wool or PIR boards are selected to achieve the required thermal resistance and maintain the energy efficiency of the space.

Technical considerations: In accordance with BS EN 13964 (Suspended ceilings – Requirements and test methods) and BS EN 520 (Gypsum plasterboards – Definitions, requirements and test methods), ceiling constructions must provide sufficient strength, deformation resistance, and compatibility with building services (lighting, ventilation, fire detection). Materials should be moisture-resistant, durable, and able to withstand mechanical damage during service.

Fire safety considerations: According to BS EN 13501-1, ceiling materials are classified by reaction to fire. Internal ceiling layers and panels should be non-combustible or of limited combustibility (e.g., A1 or A2-s1,d0), ensuring fire protection and compliance with Approved Document B.

Design life: In accordance with BS EN 13964 and BS EN ISO 15686 (Buildings and constructed assets – Service life planning), the expected service life of an internal ceiling is at least 30 years when properly designed, installed, and maintained, including protection against moisture and mechanical impacts.

Testing regime: Testing of ceiling constructions is carried out according to BS EN 13964 (load-bearing capacity and stability of suspended systems), BS EN 520 (strength and moisture resistance of gypsum plasterboards), and BS EN 13501-1 (fire performance and reaction to fire). Additionally, acoustic testing may be performed in accordance with BS EN ISO 140 and 717 to verify sound-absorbing properties.

 

L-03-05 Balcony floor build up

General information: Balcony floor build-up represents the structural layers of a balcony floor, including the supporting slab, thermal and waterproofing layers, leveling layer, and finishing surface. It ensures the durability of the structure, protection against weather effects, and comfortable use of the balcony surface.

Energy / Thermal considerations: According to BS EN ISO 6946 (Thermal performance of building components) and BS EN ISO 10211 (Thermal bridges in building construction), balcony floor constructions should minimise thermal bridges, particularly at the junction with internal spaces. Rigid insulation materials (e.g., PIR or stone wool) are used to achieve the required thermal resistance and prevent condensation formation.

Technical considerations: In accordance with BS EN 1992 (Eurocode 2: Design of concrete structures) and BS EN 13369 (Common rules for precast concrete products), balcony floor layers must withstand service loads, resist deformation, moisture exposure, and freeze-thaw cycles. Waterproofing membranes and protective coatings are selected based on durability and compatibility with finishing materials.

Fire safety considerations: According to BS EN 13501-1, materials used (waterproofing, insulation, and finishes) should be non-combustible or of limited combustibility (e.g., A1 or A2-s1,d0), preventing fire spread and ensuring compliance with fire safety requirements for external building elements.

Design life: In accordance with BS EN 1992 and BS EN ISO 15686 (Buildings and constructed assets – Service life planning), the expected service life of a balcony floor construction is at least 30 years, provided it is properly designed, installed, and maintained, including regular inspection of waterproofing and protective coatings.

Testing regime: Testing of balcony floors is carried out according to BS EN 13369 (strength and durability of concrete elements), BS EN 12390 (concrete testing), and BS EN 13501-1 (fire performance of materials). Waterproofing membranes are tested for watertightness and UV resistance, while finishing surfaces are assessed for wear resistance and slip resistance.

 

M-01-01 Horizontal fire barrier (open)

General Information: A horizontal fire barrier (open type) is a passive fire protection component installed within the cavity of ventilated façade systems. It is designed to restrict the vertical spread of fire and smoke between floors or compartments by sealing the cavity in the event of fire, while allowing ventilation and drainage under normal operating conditions. These barriers are typically installed at floor slab levels, window openings, and other fire-critical junctions.

Energy / Thermal Considerations: While its primary role is fire safety, the barrier can influence the façade's thermal continuity. To avoid cold bridging, it must be integrated without interrupting the insulation layer. This requires accurate detailing and alignment with mineral wool or other insulative materials. Thermal performance should be assessed in accordance with BS EN ISO 10211 (thermal bridges) and overall façade U-value calculations as per BS EN ISO 6946. A correctly installed fire barrier should not negatively impact thermal performance.

Technical Considerations: Barriers are typically constructed from non-combustible materials such as rock mineral wool encased in aluminium foil and secured with stainless steel fixings. They must allow unimpeded cavity ventilation under normal conditions and rapidly activate to seal the cavity under fire exposure. Design and installation must comply with BS 9991, BS 9999, and product-specific standards such as BS 476 Parts 20–22 or BS EN 1364-4 / BS EN 1366-4, depending on classification. All installations must follow the system manufacturer’s certified fire detail drawings and be compatible with the cladding system.

Fire Safety Considerations: The fire barrier must achieve a tested fire resistance rating of EI30 or EI60 (depending on project requirements) in accordance with BS EN 13501-2. Fire performance must also be verified as part of the complete façade system per BS 8414, with compliance assessed to BR 135. Materials used in the barrier must meet reaction-to-fire classification A1 or A2-s1,d0 under BS EN 13501-1. Horizontal and vertical cavity barriers are mandatory in high-rise buildings over 18 metres.

Design Life: The expected service life of the fire barrier should match or exceed that of the façade system—minimum 30 years—assuming correct specification and installation. Long-term durability requires non-combustible, corrosion-resistant materials such as stainless steel and stone wool, and adherence to relevant design codes including BS EN 1991 and BS 9999.

Testing Regime: Relevant testing includes:

  • BS EN 1364-4 / BS EN 1366-4 / BS 476 Parts 20–22 – Fire resistance performance of cavity barriers

  • BS EN 13501-1 – Reaction to fire classification of materials

  • BS EN 13501-2 – Fire resistance classification (EI30 / EI60)

  • BS 8414 + BR 135 – Full-scale façade fire testing

  • Additional product-specific testing under simulated real fire conditions, to confirm cavity sealing behaviour under high temperature and pressure.

 

M-01-04 Fire-stop

General Information: Fire-Stop is used to seal penetrations, joints, and gaps in building structures to prevent the spread of fire, smoke, and hot gases between sections of a building. It is applied in walls, floors, façades, and around service installations.

Energy / Thermal Considerations: The element must provide airtightness without creating thermal bridges. In insulated systems or ventilated façades, Fire-Stop must be compatible with insulation materials and should not reduce the energy efficiency of the building, in accordance with BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: Fire-Stop must maintain integrity and functionality under temperature fluctuations, vibration, and structural movement. The material should comply with BS EN 1366 (Fire resistance tests for service installations) and provide ease of installation and durability of connections.

Fire Safety Considerations: Fire-Stop is classified according to BS EN 13501-2 and ensures the fire resistance of floors, walls, and façades. The material prevents the spread of fire and smoke, and its performance is verified through fire resistance (EI) and smoke control testing in accordance with BS EN 1366 and BS 476.

Design Life: The expected service life of Fire-Stop is at least 30 years, provided it is installed and maintained correctly, in line with manufacturer recommendations and BS EN 1366 requirements.

Testing Regime: The material must be tested for fire resistance, smoke permeability, and durability, including tests under BS EN 1366-3 (penetration seals) and BS EN 1366-4 (linear joint seals). Compatibility with various building and service materials must also be verified.

 

M-02-01 Vertical cavity closer

General Information: A vertical cavity closer is a passive fire protection element installed within ventilated façade cavities to restrict the vertical spread of fire and smoke. It is typically used at vertical joints, abutments, panel interfaces, and the edges of window and door openings. The closer acts as a fire barrier by sealing the cavity and limiting fire propagation through the façade void.

Energy / Thermal Considerations: While its primary function is fire containment, the cavity closer must be installed to maintain thermal continuity and prevent thermal bridging. It should integrate seamlessly with the insulation layer of the façade system. Materials used—such as foil-faced mineral wool—offer low thermal conductivity. Thermal performance and detailing should be evaluated in accordance with BS EN ISO 10211 (thermal bridges) and BS EN ISO 6946 (overall U-value calculations).

Technical Considerations: The closer must be robust, dimensionally stable, and resistant to weathering and mechanical impact throughout its service life. It should form a tight, continuous seal against adjacent cladding components without compromising necessary ventilation clearances, if applicable. Typically constructed from non-combustible mineral wool encased in aluminium foil or galvanised steel. Structural and installation performance must comply with BS EN 1366-4 and BS EN 1090 (execution of steel/aluminium structures).

Fire Safety Considerations: Vertical cavity closers must achieve a fire resistance rating of at least EI30 (EI60 for buildings over 18 metres in height), and all components must meet fire reaction classifications of A1 or A2-s1,d0 under BS EN 13501-1. The closer must effectively limit vertical flame and smoke spread within the façade cavity. Compliance with BS 8414 (full-scale fire testing) and BR 135 (performance assessment) is mandatory, especially in high-rise or high-risk buildings. Closers must be installed in critical areas, including junctions, window openings, and interfaces between façade segments.

Design Life: The expected service life is at least 30 years, provided that the closer is made from durable, non-combustible materials and is installed in accordance with the system manufacturer’s guidance and relevant British Standards, including BS EN 1991 (actions on structures) and BS 9991 (fire safety in residential buildings).

Testing Regime: Vertical cavity closers must undergo the following testing:

  • BS EN 1366-4 / BS EN 1363-1 – Fire resistance testing of service installations

  • BS EN 13501-1 – Reaction to fire classification (A1 / A2-s1,d0)

  • BS EN 13501-2 – Classification based on fire resistance performance (EI30 / EI60)

  • BS 8414 + BR 135 – Full-scale fire performance testing of the façade system

  • For systems incorporating intumescent components: thermal activation testing to validate expansion behaviour and sealing performance under fire conditions.

 

M-03-01 Support bracket (fire)

General Information: A fire-rated support bracket is a mounting component designed to secure façade elements while meeting fire safety requirements. It is used to fix cladding systems and fire barriers, ensuring stability and reliability under fire conditions.

Energy / Thermal Considerations: Due to the high thermal conductivity of metals, the bracket should minimise thermal bridging. The use of thermal breaks or insulating pads at fixing points is recommended to reduce heat loss. The impact of the bracket on the thermal performance of the façade must be assessed according to BS EN ISO 10211 (thermal bridges) and BS EN ISO 6946 (overall thermal transmittance).

Technical Considerations: Brackets are typically manufactured from stainless steel or aluminium alloys with high strength and corrosion resistance, compliant with BS EN 1090-1 and BS EN 1993 (steel structures). The design must withstand calculated loads including cladding weight and wind pressure, while accommodating thermal expansion and contraction without compromising structural integrity.

Fire Safety Considerations: Materials used for the bracket must be non-combustible and achieve a minimum reaction to fire classification of A1 under BS EN 13501-1. The bracket must maintain load-bearing capacity for the duration required to support the fire barrier system, in accordance with fire resistance standards such as BS 476 and BS EN 1363.

Design Life: The expected service life is at least 30 years, assuming correct installation and maintenance. Corrosion protection methods, including stainless steel grade selection or protective coatings, extend durability in various environments.

Testing Regime: Testing includes:

  • Mechanical strength and tensile testing in accordance with BS EN ISO 6892-1

  • Corrosion resistance assessment via salt spray testing per BS EN ISO 9227

  • Fire resistance evaluation within the system context according to BS EN 13501-2 and BS 8414

 

N-01-01 Silicone sealant (for external)

General information: Silicone sealant is used for sealing construction joints, connections between façade elements, windows, doors, glazing units, as well as junctions between different materials. It provides water- and air-tightness, accommodates structural movement, and protects against moisture, dust and air infiltration.

Energy / Thermal considerations: Silicone sealants help ensure building envelope airtightness, reducing thermal losses through joints and seams. When combined with thermal insulation materials and proper installation, they contribute to compliance with air- and moisture-tightness requirements in accordance with BS EN 1026 (air permeability) and BS EN ISO 6946 (thermal performance calculation). They also prevent thermal bridging in window and façade details.

Technical considerations: Technical characteristics are regulated by BS EN 15651 (sealants for non-structural applications, including façades, windows and sanitary joints). Silicone sealant must exhibit high elasticity, adhesion to various substrates (glass, metal, PVC, concrete), and resistance to UV radiation and ageing. It should accommodate joint movement of up to ±25% or more, depending on the class. For exterior applications, compliance with movement capability and weather resistance requirements (Type F-EXT-INT according to BS EN 15651-1) is essential.

Fire safety considerations:
Most silicone sealants are classified as combustible (typically Class E or lower per BS EN 13501-1). However, special fire-resistant sealants for fire protection details may achieve classifications up to B-s1,d0 or even EI classes when tested as part of an assembly (per BS EN 1366-4 and BS EN 13501-2). Appropriate sealants must be selected according to project fire resistance requirements.

Design life: The expected service life of silicone sealant ranges from 20 to 30 years depending on environmental conditions, application quality and maintenance of proper temperature/humidity conditions. For exterior applications and movement joints, regular inspection is recommended. Durability is determined based on testing according to BS EN ISO 11600 and BS EN 15651.

Testing regime: Silicone sealants are tested to:

  • BS EN ISO 11600 (evaluation of elasticity, adhesion, ageing resistance)

  • BS EN 15651 (Parts 1-4: façades, glazing, sanitary applications, pavement joints)

  • BS EN 13501-1 or BS EN 1366-4 for fire resistance testing

  • Additional tests assess resistance to UV radiation, humidity, extreme temperatures and chemical exposure.

 

Z-01-01 Concrete slab

General information: Reinforced concrete floor slabs are designed to create load-bearing structures that distribute loads and form horizontal surfaces in buildings and civil engineering structures.

Energy/Thermal considerations: Concrete slabs must account for thermal inertia and comply with energy efficiency requirements in accordance with BS EN ISO 13786. When used in building envelope applications, they must meet thermal transmittance (U-value) requirements as specified in BS EN ISO 6946.

Technical considerations: Slabs must be designed for strength, stiffness and stability in compliance with BS EN 1992-1-1 (Eurocode 2). Reinforcement specifications, thickness and concrete grade are determined by design loads. Permissible deflections and crack resistance are regulated by BS EN 1990 and BS EN 13670.

Fire safety considerations: The fire resistance of concrete slabs must meet Class R (load-bearing capacity) and, where required, Class EI (thermal insulation and integrity) as defined in BS EN 13501-2. Minimum concrete cover thickness for reinforcement is specified in BS EN 1992-1-2.

Design life: The design service life of reinforced concrete slabs is a minimum of 50 years when maintained according to operational requirements and BS EN 1990 (structural reliability) specifications.

Testing regime: Quality control testing includes:

  • Compressive strength testing (BS EN 12390-3)

  • Freeze-thaw resistance (BS EN 12390-9)

  • Water permeability (BS EN 12390-8)

  • Reinforcement compliance verification (BS EN 10080)

  • Non-destructive testing may also be conducted (BS EN 12504-2)

 

Z-01-02 Concrete column

General information: A concrete column is used as a vertical load-bearing element of a building, transferring loads from floors and beams to the foundation. Columns provide stiffness and stability to the structure and are widely applied in both civil and industrial construction.

Energy / Thermal considerations: According to BS EN ISO 6946 and BS EN ISO 13788, concrete columns have high thermal conductivity and may act as thermal bridges within the building envelope. To reduce heat loss, the use of thermal insulation materials or thermal break solutions is required at junctions between the column and external envelope elements.

Technical considerations: In accordance with BS EN 1992-1-1 (Eurocode 2: Design of concrete structures), concrete columns must provide adequate load-bearing capacity under compression, bending, and torsion, as well as ensure crack resistance and stability. The properties of concrete and reinforcement must comply with BS EN 206 (concrete) and BS EN 1992-1-1 (reinforcement). Geometry, reinforcement, and execution class must ensure durability and conformity to the design loads.

Fire safety considerations: According to BS EN 13501-2, concrete columns can provide a fire resistance rating of REI 90–240 depending on their dimensions, concrete class, and reinforcement cover thickness. Under BS EN 13501-1, concrete is classified as a non-combustible material (Class A1), guaranteeing no contribution to fire or smoke production.

Design life: Expected design life: 50–100 years according to BS EN 1992-1-1 and BS EN 206, provided the correct concrete class is selected, reinforcement cover is ensured, and protection against aggressive environments is applied.

Testing regime: According to BS EN 206 and BS EN 1992-1-1, concrete columns are tested for compressive strength, modulus of elasticity, crack resistance, frost resistance, and durability under exposure to aggressive environments. Additional fire resistance testing is carried out in accordance with BS EN 1363-1 and BS EN 13501-2

 

Z-01-03 Concrete upstand

General information: A concrete upstand is used to create a watertight barrier at roof, terrace, balcony and other construction junctions, preventing water ingress into the building.

Energy/Thermal considerations: The concrete upstand must account for thermal bridging at interfaces with other building elements. Thermal insulation requirements and energy loss minimisation are regulated by BS EN ISO 10211 and BS EN ISO 14683.

Technical considerations: The structure must possess adequate strength and resistance to mechanical impacts. Upstand height and thickness are determined in accordance with:

  • BS 6229 (for flat roofs)

  • BS EN 1992-1-1 (for concrete structures)\

  • Waterproofing must comply with BS EN 14909 or BS 8102.

Fire safety considerations: As a non-combustible element, concrete upstands typically achieve Class A1 per BS EN 13501-1. When combined with other materials (e.g., waterproofing membranes), their fire classification must be considered.

Design life: The expected service life of a concrete upstand is minimum 30 years when properly designed, installed and waterproofed in compliance with BS 7543 (durability of building constructions).

Testing regime: Quality control includes:

  • Concrete compressive strength testing (BS EN 12390-3)

  • Water permeability testing (BS EN 12390-8)

  • Freeze-thaw resistance (BS EN 12390-9)

  • Waterproofing material adhesion and elasticity testing (BS EN 14891)

 

Z-01-05 Concrete wall

General Information: Concrete walls are used in construction as load-bearing or envelope elements, providing structural strength to the building, protection from external influences, and shaping the architectural appearance.

Energy / Thermal Considerations: In accordance with BS EN 1745 and BS EN ISO 6946, concrete walls must provide the required thermal insulation, maintain the designed thermal transmittance (U-value), and minimise thermal bridging. Where necessary, wall constructions may include insulation layers or be used as part of composite wall systems.

Technical Considerations: Concrete walls must comply with BS EN 206 (concrete — specification, performance, production, and conformity), BS EN 1992-1-1 (Eurocode 2 — design of concrete structures), and BS EN 13670 (execution of concrete structures). The construction must provide the required strength, load-bearing capacity, durability, and resistance to shrinkage and thermal deformation.

Fire Safety Considerations: According to BS EN 13501-1, concrete is classified as A1 (non-combustible), ensuring minimal contribution to fire development and no smoke production. Concrete walls provide high fire resistance and can be used for fire-rated partitions.

Design Life: The expected service life of a concrete wall is at least 50 years, provided design requirements, concrete quality, and service conditions are met, in accordance with BS EN 1990 and BS EN 206.

Testing Regime: Testing of concrete walls must be carried out in accordance with BS EN 12390 (testing of concrete specimens for strength), BS EN 1992-1-1 (design and actual structural strength), and BS EN 13670 (quality control of concrete execution). Additional tests may include frost resistance, water impermeability, and long-term durability.

VIDEOS
MODELS
TECHNICAL DOCUMENTATION