Annotations

A-01-02 Aluminium SG unitised curtain wall system

General information: The aluminium SG unitised curtain wall system is applied as a structural glazing façade, in which glass panels are fixed using silicone joints without visible external aluminium pressure plates. The system provides a modern architectural appearance of a “continuous glass façade” and is used for commercial and public buildings.

Energy / Thermal considerations: In accordance with BS EN 13830 and BS EN ISO 10077, the system must ensure a low thermal transmittance (U-value) through the use of energy-efficient insulating glass units and integrated thermal breaks in the aluminium profiles. The design is intended to minimise heat loss and improve solar control performance, in line with building energy efficiency requirements.

Technical considerations: In accordance with BS EN 13830, the façade system must provide resistance to wind loads, airtightness (BS EN 12152) and watertightness (BS EN 12154), as well as sufficient structural strength of the adhesive joints. Structural glazing silicones must comply with BS EN 13022, ensuring reliable adhesion and durability during service life.

Fire safety considerations: According to BS EN 13501-1, aluminium profiles and insulating glass units must achieve a reaction to fire classification of at least A2-s1,d0. Structural silicone joints and sealing materials are selected with consideration of fire resistance and low smoke emission. To enhance fire safety, the façade may be equipped with fire-resistant inserts and barriers in accordance with BS EN 1364.

Design life: Expected design life: 30 years according to BS EN 13830. Provided correct design, use of certified materials, and regular maintenance, the system ensures durability and operational reliability throughout its service life.

Testing regime: In accordance with BS EN 13830, BS EN 12152, and BS EN 12154, the system must undergo testing for air permeability, water tightness, and resistance to wind loads. Additional testing is carried out in accordance with BS EN 14019 for glass impact resistance, and the structural bonding of glass to profiles is verified in accordance with BS EN 13022 for durability and adhesive joint strength.

 

A-09-03 Aluminium louvre system

General Information: The aluminium louvre system is used in façade and ventilation solutions to protect buildings from direct solar radiation, regulate airflow, and provide architectural expression. It may be installed as both a decorative and functional element of curtain wall façades or window openings.

Energy / Thermal Considerations: The louvre system reduces thermal loads on the building by shielding it from solar radiation, thereby improving energy efficiency and reducing the demand for air conditioning. It complies with BS EN 14501 (Blinds and shutters – Thermal and visual comfort) and BS EN ISO 10077 with regard to the assessment of thermal performance in building envelopes.

Technical Considerations: Louvre systems must provide high rigidity, resistance to wind and operational loads, as well as corrosion resistance. Extruded aluminium profiles must comply with BS EN 755 and BS EN 12020, while protective coatings must meet BS EN 12206 (powder coating) or BS EN 12373 (anodising). The system must ensure durable connections and ease of maintenance.

Fire Safety Considerations: Aluminium, as a material, is classified as A1 according to BS EN 13501-1, meaning it is non-combustible. Coatings (painted or anodised) must also be tested as part of the system. Louvre constructions do not contribute to fire spread and may be used in areas with higher fire safety requirements.

Design Life: The expected service life of the A-09-03 Aluminium Louvre System is at least 30 years, provided proper design and operation, in accordance with BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures).

Testing Regime: The system must be tested for wind load resistance and weathering performance (BS EN 1991-1-4, BS EN ISO 9227), coating corrosion resistance (BS EN 12206), and fire classification in accordance with BS EN 13501-1. Additional tests may include BS EN 13120 (Internal blinds – Performance requirements).

 

C-01-05 Aluminium support bracket system

General Information: The aluminium support bracket system is used in ventilated façade systems with aluminium cladding for fixing and transferring loads from cladding panels to the building’s load-bearing structure. The system ensures stability, accurate positioning, and adjustment capability during installation.

Energy / Thermal Considerations: The fixing system must take into account the thermal expansion of aluminium components and their interaction with insulation, avoiding significant thermal bridging. Thermal breaks or insulating pads are applied to improve thermal performance in accordance with BS EN ISO 6946 and BS EN ISO 10211 (Thermal bridges in building construction).

Technical Considerations: Brackets and supporting profiles must have sufficient strength to resist wind and service loads in accordance with BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures). Components must be manufactured from extruded aluminium in compliance with BS EN 755 and BS EN 12020. The system must be resistant to corrosion and weathering, with protective finishes meeting BS EN 12206 (powder coating) or BS EN 12373 (anodising).

Fire Safety Considerations: Aluminium is classified as A1 under BS EN 13501-1 and is a non-combustible material. For façade applications, the fire performance of insulating pads and compatibility with cladding materials must be considered. The fixing system must not contribute to fire spread and must be tested as part of the façade assembly in accordance with BS EN 13501-2 and BS 8414 (Fire performance of external cladding systems).

Design Life: The expected service life of the aluminium support bracket system is at least 30 years when correctly installed and maintained, in compliance with BS EN 1999-1-1 and manufacturer guidance for façade systems.

Testing Regime: The system must be tested for mechanical strength and connection durability (BS EN 13144), corrosion resistance (BS EN ISO 9227), fire performance of façade systems (BS 8414, BS EN 13501-1/2), as well as climatic resistance under heating and cooling cycles.

 

C-05-01 Aluminium support bracket

General Information: An aluminium support bracket is a load-bearing component designed to connect façade systems (e.g. ventilated rainscreen or stick curtain wall systems) to the building’s primary structural frame. The bracket transfers both static and wind loads from the façade to the structural substrate and provides the necessary stand-off distance between the cladding and the building envelope.

Energy / Thermal Considerations: Aluminium brackets act as potential thermal bridges; therefore, reducing heat transfer through fixing points is essential. This can be achieved by incorporating thermal breaks, low-conductivity pads, or optimising the quantity and arrangement of metallic connections. Thermal performance should be assessed in accordance with BS EN ISO 10211 and BS EN ISO 6946. Proper insulation detailing around the bracket is critical to prevent condensation and minimise thermal losses.

Technical Considerations: Brackets must have adequate load-bearing capacity, corrosion resistance, and geometric precision. They should comply with BS EN 1090 (execution of aluminium and steel structures) and BS EN 515/573-3 (mechanical properties of aluminium alloys). Particular attention must be paid to shear and bending strength, especially at anchorage points and during load transfer to fixing elements. Resistance to fatigue and cyclic loading is also important, particularly in areas exposed to high wind pressures.

Fire Safety Considerations: Aluminium brackets are classified as non-combustible components. However, their mechanical strength significantly decreases at elevated temperatures (typically above 300–400 °C). While brackets themselves are not usually classified under BS EN 13501-1, when installed in façade systems on buildings exceeding 18 metres in height, additional fire protection measures may be required to prevent flame spread through fixing zones. Their use must be assessed as part of complete façade fire performance tests such as BS 8414 and evaluations under BR 135.

Design Life: The expected service life of aluminium support brackets is at least 30 years, in accordance with BS EN 1999 (Eurocode 9 — Design of aluminium structures), assuming protection from contact corrosion and compliance with prescribed load and environmental conditions. Anodised or powder-coated finishes further enhance corrosion resistance.

Testing Regime: Testing includes both static and dynamic load assessments according to BS EN 1090-3 and BS EN ISO 6892-1 (tensile testing of metallic materials). Corrosion resistance is evaluated using salt spray testing (BS EN ISO 9227) and environmental durability standards such as BS EN ISO 12944. Fire resistance is verified as part of full-scale façade system testing to BS 8414, while thermal performance at bracket interfaces is assessed per BS EN ISO 10211.

 

C-06-02 Stainless steel L-profile

General Information: The stainless steel L-profile is used in stone cladding systems for fixing and supporting natural or artificial stone panels. The element ensures accurate positioning, load transfer to the load-bearing structure, and long-term stability of the cladding during service life.

Energy / Thermal Considerations: Stainless steel L-brackets may create thermal bridges when penetrating through insulation layers. To minimise heat loss, thermal breaks or insulating pads are used. Thermal performance requirements are defined in BS EN ISO 6946 and BS EN ISO 10211 (Thermal bridges in building construction).

Technical Considerations: The element must provide high load-bearing capacity and resistance to bending and shear under the weight of stone panels and wind loads. Compliance is required with BS EN 1993-1-1 (Eurocode 3: Design of steel structures) and BS EN 10088 (Stainless steels – Technical delivery conditions). Stainless steel ensures corrosion resistance under external exposure, including aggressive environments.

Fire Safety Considerations: Stainless steel is classified as A1 under BS EN 13501-1 and is a non-combustible material. The L-profile does not contribute to fire spread and retains load-bearing capacity during fire exposure in accordance with BS EN 1993-1-2 (Structural fire design).

Design Life: The expected service life of the stainless steel L-profile is at least 50 years under external exposure, in compliance with BS EN 1993 and BS EN 10088, considering the corrosion resistance of stainless steel.

Testing Regime: Elements must be tested for mechanical strength and connection durability (BS EN 13144), corrosion resistance (BS EN ISO 9227), and fire performance as part of stone cladding systems in accordance with BS EN 13501-1/2 and BS 8414.

 

C-12-01 Aluminium clip

General Information: The aluminium clip is used in zinc cladding systems to fix panels to supporting brackets. It provides secure attachment, accommodates thermal movement of the zinc, and enables aesthetically concealed fixing of the cladding.

Energy / Thermal Considerations: The element is not an insulating component but must be compatible with the curtain wall system and avoid creating significant thermal bridges. In combination with pads or thermal breaks, it can contribute to improved energy performance. Requirements are defined in BS EN ISO 6946 and BS EN ISO 10211 (Thermal bridges in building construction).

Technical Considerations: Clips must have sufficient strength to retain zinc panels under wind and operational loads. Extruded or pressed aluminium should comply with BS EN 755 and BS EN 12020. Surface treatment must provide corrosion resistance in contact with zinc, in accordance with BS EN 12206 (powder coating) or anodising per BS EN 12373.

Fire Safety Considerations: Aluminium is a non-combustible material, classified as A1 under BS EN 13501-1. When used within a system incorporating zinc panels and insulation, the overall façade system’s fire performance must be verified in accordance with BS EN 13501-2 and BS 8414.

Design Life: The expected service life of the aluminium clip is at least 30 years as part of the façade system, provided correct design and corrosion protection are implemented, in accordance with BS EN 1999-1-1 (Eurocode 9: Design of aluminium structures).

Testing Regime: Elements must be tested for mechanical strength (BS EN 13144), corrosion resistance (BS EN ISO 9227), durability of connections (BS EN 755), and fire performance as part of the façade system in accordance with BS EN 13501-1/2 and BS 8414.

 

D-01-01 Aluminium Support Bracket, Fixed Point

General Information: The aluminium support bracket, designated as a fixed point for stick curtain wall systems, is employed for the rigid attachment of mullions to the primary loadbearing structure of a building. This component ensures the structural anchoring of the façade system, transmitting both vertical and horizontal loads to the structural frame.

Energy / Thermal Considerations: Although aluminium brackets do not directly influence thermal transmittance, their installation must incorporate thermal separation between the façade assembly and the loadbearing wall. In accordance with BS EN 13830, the use of thermal break pads or insulating inserts may be specified to minimise thermal bridging at anchorage points.

Technical Considerations: Brackets must comply with the mechanical performance requirements of BS EN 1999 (Eurocode 9: Design of aluminium structures) and be engineered to accommodate both permanent and variable actions, including façade self-weight, wind loads, and thermal movement. Fixed points shall provide a rigid restraint to mullions with no allowance for movement, in contrast to sliding or floating points, and must possess adequate loadbearing capacity as validated through structural analysis and performance testing. The material shall exhibit resistance to corrosion under external environmental conditions, typically through anodising or polyester powder coating.

Fire Safety Considerations: Aluminium support brackets are generally classified as non-combustible materials, potentially achieving Euroclass A1 in accordance with BS EN 13501-1. However, any associated components such as thermal break elements or gaskets must also meet relevant fire performance requirements, with classification not lower than A2-s1,d0 when assessed as part of the overall façade assembly.

Design Life: The anticipated service life of aluminium support brackets is a minimum of 30 years, subject to appropriate installation and environmental conditions, in line with BS EN 13830 and manufacturer recommendations.

Testing Regime: Testing may include verification of loadbearing capacity and deformation behaviour in accordance with BS EN 14609, which specifies test methods for structural components.

 

D-01-02 Aluminium Support Bracket, Sliding Point

General Information: The aluminium support bracket, functioning as a sliding point within stick curtain wall systems, is designed to provide flexible anchorage of mullions to the building's structural frame. Unlike fixed points, sliding connections accommodate thermal expansion and movement of the façade, thereby preventing deformation and potential damage to the system.

Energy / Thermal Considerations: As with fixed brackets, sliding point components are not direct thermal insulators. However, in accordance with BS EN 13830, façade system design must aim to minimise thermal bridging. To achieve this, thermal insulating pads may be installed between the bracket and the structural substrate.

Technical Considerations: Sliding brackets must reliably support vertical loads from the façade elements while allowing for horizontal displacement within a single plane. In accordance with BS EN 1999 (Eurocode 9: Design of aluminium structures), the bracket assembly shall be engineered to resist all relevant loads, while permitting defined movements. Adequate strength, stiffness, and resistance to displacement in unintended directions are essential. All materials used must demonstrate corrosion resistance suitable for external use and comply with BS EN 755 and BS EN 485 standards for aluminium alloys.

Fire Safety Considerations: Aluminium brackets are generally considered non-combustible and may achieve a Euroclass A1 rating as per BS EN 13501-1. Any supplementary materials used at the sliding connection—such as pads, insulators, or washers—must also be tested and classified for fire resistance to at least A2-s1,d0, if incorporated as part of the external wall build-up.

Design Life: The expected design life of sliding aluminium brackets is a minimum of 30 years, in accordance with the performance requirements for façade systems set out in BS EN 13830.

Testing Regime: Testing should verify load resistance and the operational functionality of the sliding mechanism, in line with BS EN 14609 and the broader system testing framework of BS EN 13830.

 

E-08-01 Stainless steel screw (panel to structure)

General Information: The stainless steel screw is used to fix façade panels or cladding elements to the building’s structural frame. It provides reliable anchorage, durability, and long-term stability of the façade system during service.

Energy / Thermal Considerations: Stainless steel fasteners have high thermal conductivity and can create local thermal bridges. To minimise heat loss, special pads or thermal breaks are used. Thermal performance requirements and the mitigation of thermal bridging are defined in BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: Screws must provide adequate mechanical strength and resistance to shear, pull-out, and fatigue loads. Compliance is ensured according to BS EN ISO 3506 (Mechanical properties of corrosion-resistant stainless steel fasteners). For construction use, A2 or A4 stainless steel grades are recommended depending on environmental aggressiveness. Installation must follow BS EN 1993-1-8 (Eurocode 3: Design of steel structures – Joints).

Fire Safety Considerations: Stainless steel is classified as A1 under BS EN 13501-1 and is non-combustible. During fire, screws retain mechanical strength up to temperatures defined in BS EN 1993-1-2 (Structural fire design). In façade systems, fire performance is verified according to BS EN 13501-2 and BS 8414.

Design Life: The expected service life of stainless steel screws is at least 30 years, provided the appropriate steel grade is selected (e.g., A4 for external façades in aggressive environments) and installation is correctly performed, in accordance with BS EN ISO 3506 and BS EN 1993.

Testing Regime: Screws must be tested for mechanical strength and durability (BS EN ISO 3506), corrosion resistance (BS EN ISO 9227), and the fire performance of the overall façade system (BS EN 13501-1/2 and BS 8414).

G-02-01 Weather seal membrane

General Information: The weather seal membrane is a waterproof and airtight layer used in façade and window systems to protect joints and interfaces from moisture, air, and dust ingress. It is typically applied between structural components of the building envelope (e.g. between the window frame and the wall) to provide long-lasting airtight and watertight sealing.

Energy / Thermal Considerations: The membrane contributes to the required levels of air and vapour tightness in façade systems, enhancing the building's overall energy performance by reducing infiltration-related heat loss. It must comply with BS EN 12114 (air permeability of building joints) and BS EN 13984 (vapour control layers), ensuring compatibility with the insulation system and maintaining overall airtightness. Effective vapour control and sealing are essential to meeting the thermal performance criteria outlined in BS EN ISO 6946.

Technical Considerations: The membrane must exhibit high elasticity, durability, water resistance, and the ability to maintain its mechanical integrity under joint movement and deformation. In accordance with BS EN 13984 and BS EN 13859-2 (waterproofing membranes for walls and roofs), the membrane must be resistant to UV radiation, weathering, and temperature fluctuations. Compatibility with commonly used adhesives and sealants in façade assemblies is also essential.

Fire Safety Considerations: Weather seal membranes are typically classified as Class E under BS EN 13501-1. Their use is generally permitted in buildings under 18 metres in height, in line with current façade fire safety guidance and regulations. For buildings exceeding this height, membranes with a higher fire resistance classification are required.

Design Life: The expected service life of the membrane is approximately 25–30 years, provided it is correctly installed and protected from mechanical damage and prolonged UV exposure. Long-term durability and performance are supported by accelerated ageing and climate resistance testing as per BS EN 1296 and BS EN 13859-2.

Testing Regime: The membrane should be tested in accordance with the following standards:

  • BS EN 13859-2 – mechanical strength and water resistance;

  • BS EN 1928 – watertightness testing;

  • BS EN 12114 – air permeability performance;

  • BS EN 1296 – artificial ageing;

  • BS EN 13501-1 – fire classification (typically Class E).

G-04-01 Mineral wool insulation (for external application) (k ≤ 0.035 W/mK)

General Information: Mineral wool insulation (for wall) is used in external and internal building envelopes to provide thermal, acoustic and fire insulation. Installed in multi-layer walls, façade systems or framed partitions as a non-combustible insulation material.

Energy/Thermal Considerations: Mineral wool features low thermal conductivity (λ ≈ 0.032-0.040 W/m·K), complying with BS EN 13162 - the standard for thermal insulation products for buildings. It effectively reduces heat loss and helps building envelopes meet energy efficiency requirements (e.g. BS EN ISO 6946). Insulation thickness is selected based on required U-value.

Technical Considerations: According to BS EN 13162, mineral wool must maintain dimensional stability, moisture resistance, compressive strength (when used in rainscreen systems), and long-term durability. The material must retain its insulating properties under humid conditions. For walls, compliance with strength classes and dimensional stability under temperature fluctuations is essential. Capillary activity and water vapour diffusion resistance (µ-factor) are also considered.

Fire Safety Considerations: Mineral wool is a non-combustible material typically classified as A1 per BS EN 13501-1 - it doesn't support combustion, emit toxic gases or produce flaming droplets. Used as a component in fire protection systems for façades, partitions and fire compartments. When used in external insulation systems (e.g. ventilated façades), it ensures structural fire safety.

Design Life: The expected service life of mineral wool is minimum 30 years per BS EN 13162, provided proper installation, moisture protection and avoidance of mechanical damage.

Testing Regime: Testing is conducted according to BS EN 13162 and BS EN 1602-1609, including determination of thermal conductivity, water absorption, compressive strength, ageing resistance and dimensional stability. Fire performance is verified per BS EN 13501-1.

G-07-01 Insulation wall panel

General information: Insulation Wall Panel is used in external and internal wall constructions to enhance the energy efficiency of buildings. It provides thermal insulation, improves acoustic comfort, and can serve as decorative or protective cladding.

Energy / Thermal considerations: Insulated wall panels have low thermal conductivity and must comply with energy performance requirements according to BS EN ISO 6946 (Building components and building elements – Thermal resistance and transmittance) and BS EN 13165/13162 (depending on insulation type, e.g., PIR or mineral wool). Panels should minimise heat loss and reduce the risk of thermal bridging.

Technical considerations: Insulation Wall Panels must have sufficient strength and rigidity to withstand mechanical loads, including wind pressure, while maintaining dimensional stability under temperature and humidity variations. Materials and construction should comply with BS EN 14509 (Self-supporting double skin metal faced insulating panels) or BS EN 13162/13165 for insulation products.

Fire safety considerations: Panel fire performance depends on the insulation material. Mineral wool panels provide A1 or A2 classification under BS EN 13501-1, while PIR and other polymer-based insulations may have lower ratings (e.g., B-s2,d0). Panel selection for façades and internal walls should consider fire resistance requirements in accordance with BS EN 13501-2.

Design life: The expected service life of Insulation Wall Panels is at least 30 years according to BS EN 14509 or the relevant insulation standard, provided correct installation and maintenance.

Testing regime: Panels should be tested for thermal conductivity (BS EN 12667), mechanical strength (BS EN 14509), fire performance (BS EN 13501-1/2), moisture absorption, and durability.

 

H-02-01 Double glazed unit (DGU-1)

General Information: A double glazed unit (DGU) is used in window, door, and façade systems to provide thermal and acoustic insulation. It consists of two glass panes separated by a spacer frame with a hermetically sealed cavity, which may be filled with air or an inert gas (e.g., argon). DGUs are employed in residential, commercial, and industrial buildings to enhance energy efficiency and comfort.

Energy / Thermal Considerations: According to BS EN 1279 (standards for insulating glass units), a double glazed unit must achieve a low thermal transmittance (U-value), particularly when using low-emissivity coatings (Low-E) and gas filling. This ensures compliance with building energy efficiency requirements, as specified in BS EN ISO 10077-1 and BS EN ISO 10456. The use of inert gases and warm-edge spacer bars further reduces heat loss and the risk of condensation.

Technical Considerations: Technical requirements for double glazed units are defined by BS EN 1279 (Parts 1–6), covering durability, airtightness, moisture absorption, optical properties, and thickness tolerances. Additional parameters include sound insulation, wind load resistance, and impact resistance (where required). Compatibility with window or façade systems must be ensured in accordance with BS EN 14351-1 (windows and external pedestrian doors).

Fire Safety Considerations: Standard double glazed units made from tempered or float glass are not fire-resistant, though they may be used in non-fire-rated barriers. Their behaviour in fire depends on the glass type: standard glass is not classified under BS EN 13501-1, but tempered or laminated glass may meet certain safe breakage requirements. If the glazed unit is part of a fire-rated system, specialist fire-resistant glass certified to BS EN 14449 and BS EN 13501-2 must be used.

Design Life The expected service life of a double glazed unit is at least 25–30 years, assuming proper installation and sealing quality, as per BS EN 1279-2 and -3.

Testing Regime: Testing includes assessments for:

  • Airtightness (BS EN 1279-2)

  • Moisture absorption (BS EN 1279-3)

  • Thermal transmittance (BS EN 674)

  • Light transmittance (BS EN 410)

  • Sound insulation (BS EN ISO 10140)

  • Resistance to climatic cycling and ageing

  • Full-scale testing of glazed units within window systems is conducted under BS EN 14351-1.

H-02-02 Double glazed unit (DGU-2)

General Information: A double glazed unit (DGU) is used in window, door, and façade systems to provide thermal and acoustic insulation. It consists of two glass panes separated by a spacer frame with a hermetically sealed cavity, which may be filled with air or an inert gas (e.g., argon). DGUs are employed in residential, commercial, and industrial buildings to enhance energy efficiency and comfort.

Energy / Thermal Considerations: According to BS EN 1279 (standards for insulating glass units), a double glazed unit must achieve a low thermal transmittance (U-value), particularly when using low-emissivity coatings (Low-E) and gas filling. This ensures compliance with building energy efficiency requirements, as specified in BS EN ISO 10077-1 and BS EN ISO 10456. The use of inert gases and warm-edge spacer bars further reduces heat loss and the risk of condensation.

Technical Considerations: Technical requirements for double glazed units are defined by BS EN 1279 (Parts 1–6), covering durability, airtightness, moisture absorption, optical properties, and thickness tolerances. Additional parameters include sound insulation, wind load resistance, and impact resistance (where required). Compatibility with window or façade systems must be ensured in accordance with BS EN 14351-1 (windows and external pedestrian doors).

Fire Safety Considerations: Standard double glazed units made from tempered or float glass are not fire-resistant, though they may be used in non-fire-rated barriers. Their behaviour in fire depends on the glass type: standard glass is not classified under BS EN 13501-1, but tempered or laminated glass may meet certain safe breakage requirements. If the glazed unit is part of a fire-rated system, specialist fire-resistant glass certified to BS EN 14449 and BS EN 13501-2 must be used.

Design Life The expected service life of a double glazed unit is at least 25–30 years, assuming proper installation and sealing quality, as per BS EN 1279-2 and -3.

Testing Regime: Testing includes assessments for:

  • Airtightness (BS EN 1279-2)

  • Moisture absorption (BS EN 1279-3)

  • Thermal transmittance (BS EN 674)

  • Light transmittance (BS EN 410)

  • Sound insulation (BS EN ISO 10140)

  • Resistance to climatic cycling and ageing

  • Full-scale testing of glazed units within window systems is conducted under BS EN 14351-1.

 

H-04-01 Aluminium spandrel panel (ASP-1)

General information: Aluminium spandrel panels are used to cover floor slabs in façade systems, as well as for decorative purposes and to provide enclosure. The panels are installed in the zones between window openings and are non-transparent elements, ensuring architectural expression and protecting internal structures from weather exposure.

Energy / Thermal considerations: In accordance with BS EN ISO 6946 (Thermal performance of building components) and BS EN ISO 10077 (Thermal performance of windows, doors and shutters), aluminium spandrel panels must incorporate an insulating layer or suitable backing to eliminate thermal bridging and achieve the required thermal resistance. The panel design must maintain the energy efficiency of the building envelope and prevent condensation.

Technical considerations: According to BS EN 485 and BS EN 573 (Aluminium and aluminium alloys), panels must be manufactured from alloys with adequate strength, corrosion resistance and dimensional stability. Mechanical reliability, weathertightness and durability requirements for façade assemblies are defined in BS EN 13830 (Curtain walling – Product standard). The panel must be compatible with the supporting façade system and capable of withstanding wind loads and service loads.

Fire safety considerations: In accordance with BS EN 13501-1, aluminium is classified as a non-combustible material (Class A1). However, the construction of spandrel panels includes insulation and facing layers, which must comply with the requirements of Approved Document B. To ensure fire safety, non-combustible insulation materials (e.g. mineral wool classified as A1 or A2-s1,d0) and non-combustible facing materials must be used within the panel assembly, in line with BS EN 1364 (Fire resistance tests for non-loadbearing elements).

Design life: In accordance with BS EN 13830 and BS EN 1999 (Eurocode 9: Design of aluminium structures), the expected service life of aluminium spandrel panels is at least 30 years, provided correct design, installation and corrosion protection are ensured.

Testing regime: Testing of aluminium spandrel panels is carried out in accordance with BS EN 13830 (mechanical performance, air permeability, watertightness), BS EN 13501-1 (fire performance classification), and BS EN ISO 10077 (thermal performance). Additional corrosion resistance tests may be carried out in accordance with BS EN ISO 9227 (salt spray test)

 

I-01-01 Aluminium panel

General Information: Aluminium panels are thin-gauge cladding elements used in ventilated façade systems for both decorative and protective purposes. Installed using either visible or concealed fixings, they form part of the building envelope, shielding the structure from environmental exposure while contributing to modern architectural aesthetics.

Energy / Thermal Considerations: Due to their high thermal conductivity, aluminium panels do not serve as insulation. However, as external components of a ventilated façade system, they are critical in protecting underlying thermal insulation from wind and moisture ingress. Thermal performance calculations must be carried out in accordance with BS EN ISO 6946 and BS EN ISO 10211, with particular attention paid to thermal bridging around fixings. Adequate rear ventilation behind the panel is essential to allow moisture drainage and pressure equalisation.

Technical Considerations: Aluminium panels must be resistant to deformation, vibration, corrosion, and thermal cycling. Base materials should comply with BS EN 485 (rolled aluminium products), BS EN 573-3 and BS EN 515 (alloy and mechanical property specifications). Panel thickness and type (e.g. solid aluminium or aluminium composite) are selected based on wind load analysis per BS EN 1991-1-4 and material rigidity. Aesthetic and functional considerations include UV resistance, colour stability, and abrasion resistance of coatings.

Fire Safety Considerations: Fire performance depends on the panel type. Solid aluminium panels are typically non-combustible and may be classified as Class A1 per BS EN 13501-1. Aluminium composite panels (ACP) must have non-combustible cores (e.g. mineral-filled) to be used on buildings over 18 metres in height, achieving at least Class A2-s1,d0. The use of combustible cores (e.g. polyethylene) in high-rise or critical buildings is prohibited. All cladding products should be installed as part of façade systems tested to BS 8414 and assessed in accordance with BR 135.

Design Life: Aluminium panels have an expected service life of 30 years or more, subject to the quality of the coating and environmental conditions. Coating performance in terms of UV durability, pollution resistance and corrosion protection must meet BS EN 12206 (coated aluminium products). In coastal or industrial environments, additional protective measures or corrosion-resistant aluminium grades are recommended.

Testing Regime: Applicable testing standards include:

  • BS EN 13501-1 – Fire classification (A1 or A2-s1,d0)

  • BS EN 485 / BS EN ISO 6892-1 – Mechanical properties of aluminium sheet

  • BS EN 12206 – Coating quality and weathering resistance

  • BS EN ISO 9227 – Salt spray (neutral) testing for corrosion resistance

  • BS 8414 and BR 135 – Full-scale fire performance as part of cladding system

 

I-03-01 Stone panel

General Information: Stone panels are used in ventilated façade systems and interior applications for cladding buildings with natural or engineered stone. They provide durability, aesthetic appeal, and protection of the structure from external influences.

Energy / Thermal Considerations: Stone has high thermal conductivity and does not provide insulation. When used in façade systems, it must be combined with thermal insulation materials to minimise heat loss and prevent thermal bridging. Requirements are governed by BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: Panels must have sufficient strength and rigidity to withstand their own weight, wind loads, and operational stresses. Fixings and installation should comply with BS EN 1991-1-4 (Wind actions) and BS EN 1993-1-1 / BS EN 1992-1-1 (Eurocode 3 / 2: Design of steel / concrete structures) for load transfer to the supporting structure. The stone must be resistant to weathering, chemically inert, and durable.

Fire Safety Considerations: Both natural and engineered stone are classified as A1 under BS EN 13501-1, making them non-combustible and not contributing to fire spread. The overall fire performance of the façade system should be verified according to BS EN 13501-2 and BS 8414.

Design Life: The expected service life of stone panels is 50–100 years, depending on the type of stone and conditions of use, in accordance with BS EN 12057 (Natural stone products – Slabs for cladding) and BS EN 1469 (Natural stone products – Tiles for internal and external floors and walls).

Testing Regime: Panels should be tested for strength, frost resistance, and water absorption (BS EN 12371, BS EN 1469), as well as for durability against weathering. Fire performance testing of the façade system should be conducted in accordance with BS EN 13501-2 and BS 8414.

 

I-11-01 Zinc sheet

General Information: Zinc sheet is used in ventilated façade and roofing systems for building cladding. It provides durability, corrosion resistance, and an aesthetically pleasing finish. The material can be applied either as rolled sheets or pre-fabricated panels.

Energy / Thermal Considerations: Zinc has high thermal conductivity and does not provide thermal insulation by itself. When used in façade systems, it must be integrated with insulation materials. Systems should comply with BS EN ISO 6946 (Thermal resistance and transmittance) and BS EN ISO 10211 (Thermal bridges in building construction) to minimise heat loss and prevent thermal bridging.

Technical Considerations: Zinc sheets must have sufficient thickness and strength to withstand wind and operational loads, as well as resistance to deformation and corrosion. The material should comply with BS EN 988 (Zinc and zinc alloys – Specifications for rolled flat products for building) and BS EN 1179 (Zinc and zinc alloys – Refining zinc). The fixing system must allow for thermal expansion compensation.

Fire Safety Considerations: Zinc is classified as A1 under BS EN 13501-1 and is non-combustible. Within ventilated façade systems, it does not contribute to fire spread and is suitable for buildings with higher fire safety requirements. Overall fire performance of the system should be verified according to BS EN 13501-2 and BS 8414.

Design Life: The expected service life of zinc sheet is 40–60 years, depending on thickness, surface treatment, and operating conditions, in accordance with BS EN 988 and manufacturer recommendations.

Testing Regime: The material must be tested for mechanical properties (BS EN 988), corrosion resistance (BS EN ISO 9227), durability of connections, and compatibility with fasteners. Zinc-based façade systems must undergo fire performance testing as part of the system according to BS EN 13501-1/2 and BS 8414.

 

L-03-03 Rain drainage channel

General information: Rain drainage channels are used to divert rainwater and meltwater from the surfaces of pavements, roads, and areas adjacent to buildings. The channel system protects foundations and surfaces from excessive moisture, prevents water stagnation, and improves the safety of outdoor areas.

Energy / Thermal considerations: According to BS EN 1433 (drainage channels for pedestrian and vehicular areas), the system must maintain stability and performance under exposure to moisture, temperature fluctuations, and freeze–thaw cycles. The channel construction does not directly influence the thermal performance of a building; however, it protects adjacent structures from moisture, thereby helping to maintain the designed energy efficiency of the envelope.

Technical considerations: In accordance with BS EN 1433, channels must provide strength appropriate to the load class (from A15 for pedestrian areas to F900 for carriageways). The material (concrete, polymer concrete, stainless steel, or composites) must be resistant to water, chemical agents, and mechanical loads. The design includes gratings for debris collection as well as provisions for easy cleaning and maintenance.

Fire safety considerations: According to BS EN 13501-1, channels made of concrete or steel are classified as A1 (non-combustible). Polymer and composite variants must demonstrate a fire reaction class of at least B-s1,d0. Design must take into account the placement of channels near buildings and systems, ensuring compliance with fire safety requirements in accordance with BS EN 13501-2.

Design life: Expected design life: 30–50 years according to BS EN 1433, provided the appropriate load class is selected and regular cleaning and maintenance are carried out.

Testing regime: According to BS EN 1433, channels are tested for load-bearing capacity, hydraulic capacity, resistance to chemical agents, freeze–thaw durability, and long-term performance. Additional classification is conducted for fire reaction in accordance with BS EN 13501-1.

 

M-01-04 Fire-stop

General Information: Fire-Stop is used to seal penetrations, joints, and gaps in building structures to prevent the spread of fire, smoke, and hot gases between sections of a building. It is applied in walls, floors, façades, and around service installations.

Energy / Thermal Considerations: The element must provide airtightness without creating thermal bridges. In insulated systems or ventilated façades, Fire-Stop must be compatible with insulation materials and should not reduce the energy efficiency of the building, in accordance with BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: Fire-Stop must maintain integrity and functionality under temperature fluctuations, vibration, and structural movement. The material should comply with BS EN 1366 (Fire resistance tests for service installations) and provide ease of installation and durability of connections.

Fire Safety Considerations: Fire-Stop is classified according to BS EN 13501-2 and ensures the fire resistance of floors, walls, and façades. The material prevents the spread of fire and smoke, and its performance is verified through fire resistance (EI) and smoke control testing in accordance with BS EN 1366 and BS 476.

Design Life: The expected service life of Fire-Stop is at least 30 years, provided it is installed and maintained correctly, in line with manufacturer recommendations and BS EN 1366 requirements.

Testing Regime: The material must be tested for fire resistance, smoke permeability, and durability, including tests under BS EN 1366-3 (penetration seals) and BS EN 1366-4 (linear joint seals). Compatibility with various building and service materials must also be verified.

 

M-01-07 Closed-State Cassette Infill

General Information: The Close State Cassette Infill is used in ventilated façade systems as an infill component to provide fire protection and seal cavities between cladding panels and the supporting structure. It prevents the spread of fire, smoke, and hot gases through the façade.

Energy / Thermal Considerations: The element must maintain the thermal integrity of the façade system, minimising heat loss and eliminating thermal bridges. Its design should be compatible with insulation materials and comply with BS EN ISO 6946 and BS EN ISO 10211.

Technical Considerations: The Cassette Infill must provide high strength, dimensional stability, and resistance to deformation under heating. The material should comply with BS EN 1366 (Fire resistance tests for service installations) and BS EN 13162 (Thermal insulation products for buildings – Factory made mineral wool products) when used in combination with insulation. It must be durable and retain performance under exposure to moisture and temperature fluctuations.

Fire Safety Considerations: The Close State Cassette Infill must comply with BS EN 13501-1 (Reaction to fire) and achieve a fire classification of at least A2-s1,d0. The effectiveness of the complete façade system incorporating this component must be verified through testing in accordance with BS EN 13501-2 and large-scale façade tests to BS 8414.

Design Life: The expected service life of the Close State Cassette Infill is at least 30 years under correct installation and maintenance, in accordance with manufacturer recommendations and BS EN 1366.

Testing Regime: The element should be tested for fire resistance to EI criteria (integrity and insulation) in accordance with BS EN 1366-4 (linear joint seals) and BS EN 1366-3 (penetration seals), as well as system-level fire performance tests to BS EN 13501-2 and BS 8414.

 

M-02-01 Vertical cavity closer

General Information: A vertical cavity closer is a passive fire protection element installed within ventilated façade cavities to restrict the vertical spread of fire and smoke. It is typically used at vertical joints, abutments, panel interfaces, and the edges of window and door openings. The closer acts as a fire barrier by sealing the cavity and limiting fire propagation through the façade void.

Energy / Thermal Considerations: While its primary function is fire containment, the cavity closer must be installed to maintain thermal continuity and prevent thermal bridging. It should integrate seamlessly with the insulation layer of the façade system. Materials used—such as foil-faced mineral wool—offer low thermal conductivity. Thermal performance and detailing should be evaluated in accordance with BS EN ISO 10211 (thermal bridges) and BS EN ISO 6946 (overall U-value calculations).

Technical Considerations: The closer must be robust, dimensionally stable, and resistant to weathering and mechanical impact throughout its service life. It should form a tight, continuous seal against adjacent cladding components without compromising necessary ventilation clearances, if applicable. Typically constructed from non-combustible mineral wool encased in aluminium foil or galvanised steel. Structural and installation performance must comply with BS EN 1366-4 and BS EN 1090 (execution of steel/aluminium structures).

Fire Safety Considerations: Vertical cavity closers must achieve a fire resistance rating of at least EI30 (EI60 for buildings over 18 metres in height), and all components must meet fire reaction classifications of A1 or A2-s1,d0 under BS EN 13501-1. The closer must effectively limit vertical flame and smoke spread within the façade cavity. Compliance with BS 8414 (full-scale fire testing) and BR 135 (performance assessment) is mandatory, especially in high-rise or high-risk buildings. Closers must be installed in critical areas, including junctions, window openings, and interfaces between façade segments.

Design Life: The expected service life is at least 30 years, provided that the closer is made from durable, non-combustible materials and is installed in accordance with the system manufacturer’s guidance and relevant British Standards, including BS EN 1991 (actions on structures) and BS 9991 (fire safety in residential buildings).

Testing Regime: Vertical cavity closers must undergo the following testing:

  • BS EN 1366-4 / BS EN 1363-1 – Fire resistance testing of service installations

  • BS EN 13501-1 – Reaction to fire classification (A1 / A2-s1,d0)

  • BS EN 13501-2 – Classification based on fire resistance performance (EI30 / EI60)

  • BS 8414 + BR 135 – Full-scale fire performance testing of the façade system

For systems incorporating intumescent components: thermal activation testing to validate expansion behaviour and sealing performance under fire conditions.

 

Z-01-01 Concrete slab

General information: Reinforced concrete floor slabs are designed to create load-bearing structures that distribute loads and form horizontal surfaces in buildings and civil engineering structures.

Energy/Thermal considerations: Concrete slabs must account for thermal inertia and comply with energy efficiency requirements in accordance with BS EN ISO 13786. When used in building envelope applications, they must meet thermal transmittance (U-value) requirements as specified in BS EN ISO 6946.

Technical considerations: Slabs must be designed for strength, stiffness and stability in compliance with BS EN 1992-1-1 (Eurocode 2). Reinforcement specifications, thickness and concrete grade are determined by design loads. Permissible deflections and crack resistance are regulated by BS EN 1990 and BS EN 13670.

Fire safety considerations: The fire resistance of concrete slabs must meet Class R (load-bearing capacity) and, where required, Class EI (thermal insulation and integrity) as defined in BS EN 13501-2. Minimum concrete cover thickness for reinforcement is specified in BS EN 1992-1-2.

Design life: The design service life of reinforced concrete slabs is a minimum of 50 years when maintained according to operational requirements and BS EN 1990 (structural reliability) specifications.

Testing regime: Quality control testing includes:

  • Compressive strength testing (BS EN 12390-3)

  • Freeze-thaw resistance (BS EN 12390-9)

  • Water permeability (BS EN 12390-8)

  • Reinforcement compliance verification (BS EN 10080)

  • Non-destructive testing may also be conducted (BS EN 12504-2)

 

Z-02-01 Steel column

General information: A steel column is used as a vertical load-bearing element of a building frame, transferring loads from slabs, beams, and roofs to the foundation. It is widely used in residential, industrial, and high-rise buildings due to its high load-bearing capacity relative to small cross-sections and fast installation speed.

Energy / Thermal considerations: According to BS EN ISO 6946 and BS EN ISO 13788, steel columns have high thermal conductivity and can create significant thermal bridges at junctions with the building envelope. To maintain the building’s calculated energy efficiency, thermal break elements or external insulation are applied at points where the column passes through the envelope.

Technical considerations: In accordance with BS EN 1993-1-1 (Eurocode 3: Design of steel structures), steel columns must be designed for compression, bending, and combined loading, taking into account stability, slenderness, and steel ductility. The steel should comply with BS EN 10025 (hot-rolled sections) or BS EN 10210/10219 (hollow sections). All connections are executed in accordance with BS EN 1090, considering welded or bolted joints. Corrosion protection is provided in line with BS EN ISO 12944.

Fire safety considerations: According to BS EN 13501-2, unprotected steel columns lose load-bearing capacity at approximately 500–600 °C. Therefore, depending on the building’s fire-resistance requirements, protective cladding, sprayed coatings, or intumescent paints are applied in accordance with BS EN 13381. Steel is classified as non-combustible (Class A1 under BS EN 13501-1) but requires protection to achieve fire-resistance ratings of R30–R120.

Design life: Expected design life: 50–100 years according to BS EN 1993-1-1 and BS EN 1090, provided correct design, corrosion protection, and fireproofing measures are applied.

Testing regime: According to BS EN 1090 and BS EN 1993, steel columns are tested for strength, stability, geometric accuracy, and quality of welded and bolted connections. Fire-protection systems are tested in accordance with BS EN 13381, and fire-resistance classification is carried out according to BS EN 13501-2.

 

Z-02-02 Steel beam

General information: A steel beam is utilised as a primary horizontal load-bearing element within building and civil engineering structures. It serves to transfer loads from floors, walls, roofs, and other components to columns, walls, or foundations. Steel beams are extensively employed in residential, commercial, and industrial construction, including both framed and monolithic systems.

Energy / Thermal considerations: Although a steel beam itself is not a thermal insulation element, its penetration through building envelopes (e.g. external walls) can create thermal bridges. In accordance with BS EN ISO 10211, heat transfer through metallic elements must be considered in thermal modelling of buildings. Thermal losses can be minimised by incorporating thermal breaks or insulating pads at connection points.

Technical considerations: Steel beams are designed and calculated in accordance with BS EN 1993-1-1 (Eurocode 3: Design of steel structures). They must satisfy requirements for strength, stiffness, stability, and permissible deformations under permanent and variable loads. Compliance with BS EN 10025 (technical delivery conditions for structural steel) and BS EN 1090 (requirements for execution of steel structures) is mandatory. Consideration must be given to welding and bolted connections, as well as corrosion protection methods such as galvanising, painting, or fire-protective coatings.

Fire safety considerations: Steel loses strength at elevated temperatures; therefore, steel beams require fire protection in accordance with BS EN 1993-1-2. Minimum fire resistance periods (e.g. 30, 60, 90 minutes) are prescribed by regulations and can be achieved through the application of fire-retardant paints, encasements, or cladding. Fire resistance classification is conducted pursuant to BS EN 13501-2. Unprotected steel beams do not comply with fire resistance requirements.

Design life: The typical service life of a steel beam is 50 years or more, provided corrosion and fire protection measures are properly implemented, in line with BS EN 1990 (basis of structural design) and BS EN 1993. Actual durability depends on operating conditions and quality of protective measures.

Testing regime: Testing includes verification of mechanical properties of steel according to BS EN 10025 (e.g. yield strength, tensile strength), weld qualification per BS EN ISO 15614, and fire resistance tests (BS EN 1365 or BS EN 13381 for protective methods). Manufacturing and installation processes must comply with CE marking requirements as per BS EN 1090. 

VIDEOS
MODELS
TECHNICAL DOCUMENTATION